Specifi cations
Approvals & codes
These appliances are certifi ed by ANSI Z21.88-2017/CSA
2.33-2017 American National Standard / CSA Standard
for
Vented Gas Fireplace Heaters
for use in Canada and
USA. These appliances are for installation directly venting
through an outside wall or through the roof.
Conversion between fuels may only be done using the
approved conversion kits listed in the section
Options
.
These appliances comply with CSA P.4.1-15
Testing
method for measuring annual
fi
replace e
ffi
ciencies
.
The installation must conform with local codes or, in
the absence of local codes with the
National Fuel Gas
Code, ANSI Z223.1/NFPA 54
or the
Natural Gas and
Propane Installation Code CAN/CGA-B149.1
. Only
qualifi ed licensed or trained personnel should install
these appliances.
These appliances, when installed, must be electrically
grounded in accordance with local codes or, in the
absence of local codes, with the
National Electrical
Code, ANSI/NFPA 70
or the
Canadian Electrical Code,
CSA C22.1
.
Ratings
*Tested to
CGA - 2.17-91 High Altitude Standard in
Canada
. In the USA, installations may require deration
over 2000 feet—check local codes.
*High Altitude Installations
Input ratings are shown in BTU per hour and are
certifi ed without deration for elevations up to
4,500 feet (1,370 m) above sea level.
For elevations above 4,500 feet (1,370 m) in USA,
installations must be in accordance with the current
ANSI Z223.1 and/or local codes having jurisdiction.
Heating value of gas in some areas is reduced to
compensate for elevation—consult your local gas
utility to confi rm.
For installations at elevations above 4,500 feet
(1,370 m) in Canada, please consult provincial
and/or local authorities having jurisdiction.
Supply Gas
Heater engine units 534JN is used with natural gas
installations.
Heater engine units 534JP is used with propane gas
installations.
The supply pressure
must be between the
limits shown in the table
above.
The supply connection is
⅜ inch NPT.
The opening for the
gas supply line is at the
left side of the
appliance.
Venting options
Co-axial direct vent installations (solid piping)
A list of all approved venting accessories starts on
page 48 of this manual.
NOTE: An 817VAK Vent Adapter is required in all
cases.
Co-linear direct vent installations (fl exible piping)
Converts the appliance outlet collars to accept two
3-inch diameter fl ex liners for installation into existing
solid-fuel burning fi replaces and chimneys. Requires a
co-linear adapter at the appliance and either a co-linear
terminal or co-linear-to-co-axial adapter and terminal
at the top of the chimney. A list of approved venting
accessories starts on page 48 of this manual.
X
X
This appliance is designed and approved as a
supplemental heater and provides the potential
for most energy conservation when used while
attended. The use of an alternate primary heat
source is advisable.
Outdoor Conversion Kit
The 534J model is supplied standard for indoor
applications and may be adapted for installation in
specifi c “outdoor” applications protected from weather
as defi ned in the GV60CKO outdoor conversion kit
manual.
WARNING
O p t i o n a l e l e c t r i c a l a c c e s s o r i e s
A R E N O T A L L O W E D w h e n a d a p t i n g
a p p l i a n c e f o r o u t d o o r u s e .
!
Model
JN
JP
Gas
Natural Propane
Altitude (Ft.)*
0-4,500 feet*
Input Maximum (Btu/h)
24,000
24,000
Input Minimum (Btu/h)
6,500
13,000
Manifold Pressure (in w.c.)
3.95
10.0
Min. Supply Pressure (in w.c.)
5.0
11.0
Max. Supply Pressure (in w.c.)
11.0
14.0
QUALIFIED
INSTALLER