INSTALLER’S GUIDE
Page 9
1
Though the total height of the closure plate will accommodate a maximum opening
height of 650mm, heights above 610mm will leave the closure plate and sealing tape
visible above the appliance.
2
Any opening visible below the appliance may be closed in.
4.9.4
Metal Flue Box
The appliance can be installed to a metal flue box conforming to BS715 Section 6 (For
gas fires to BS5258: Part 5) having a minimum internal depth of 165mm.
The opening must be within the following dimensions:
Width
Max.
440mm
Min.
380mm
Height
Max.
610mm
★
Min.
525mm
★
Though the total height of the closure plate will accommodate a maximum opening
height of 650mm, heights above 610mm will leave the closure plate and sealing tape
visible above the appliance.
4.10
If the fireplace opening is greater than the acceptable dimensions given in this
guide, do not use the back of a fire surround or marble to reduce the opening. This
may cause cracking of the surround back or marble
.
4.11
The following flues are suitable:
•
225mm x 225mm conventional brick flue.
If a flue liner is used, it must be a minimum of 125mm diameter. The liner must be sealed
to the surrounding area above the fireplace opening and to the top of the chimney. An
approved terminal must be fitted.
•
A properly constructed precast flue conforming to B.S 1289 or BS EN 1806.
•
A flue pipe with a minimum diameter of 127mm. See B.S 6461 Part 1 for suitable
materials. Metal flue pipes must comply with B.S 715. See section 4.9.4 of this guide for
flue box opening sizes.
4.11.1
The flue must conform to BS 5440: Part 1 in design and installation.
The flue, measured from the bottom of the fireplace opening to the bottom of the
terminal, shall be not less than 3m in actual vertical height. When calculated in
accordance with BS 5440: Part 1 Annex A, the minimum
equivalent
height of the flue
shall be 2.0m of 125mm dia. flue pipe.
4.11.2
The flue must be clear of any obstruction and its base must be clear of debris.
4.11.3
The flue must be completely sealed so that combustion products do not come into
contact with combustible materials outside the chimney.
4.11.4
The flue must serve only one fireplace.
4.11.5
Proprietary terminals must comply with BS 715 or BS 1289. Any terminal or
termination must be positioned in accordance with BS 5440 Part 1 to ensure that the