INSTALLER’S GUIDE
Page 17
Figure 11 Case top location
Figure 12. Spillage
check
8 O U T E R C A S E F I T T I N G
•
Remove the control knob from the spindle.
•
Refit the outer case. The outer case top rear
strip should locate in front of, but touching,
the side extensions of the engine back panel.
See figure 11.
•
Secure the case at the bottom sides with the
two screws previously removed.
•
Fit the control knob fully over the gas tap
spindle.
9 S P I L L A G E C H E C K
A spillage test must be made before the installed appliance is left with the customer.
1.
Close all doors and windows in the room containing the
fire.
2.
Light the appliance and set the control knob to the
maximum position (Position 5).
3.
Leave the appliance on for five minutes.
4.
Place a smoke match tube (with lighted match)
horizontally underneath the radiant box but touching the top
lip of the box. The tube should be between the two vertical
inner ribs of the centre radiant. The tip of the match should
project between 2mm and 5mm beyond the lowest edge of
the
radiant box lip
(The radiant box lip is behind the black
outer case panel). See figure 12.
5.
The installation is satisfactory if the smoke is drawn into
the appliance. If the smoke is not drawn into the appliance,
leave the appliance alight at the maximum setting for a
further ten minutes and then repeat the test. If the smoke is still not drawn into the
appliance, inspect the sealing of the closure plate. If the sealing is satisfactory but the
appliance is installed with the flue restrictor in the closed position (see section 6.5),
reopen the restrictor, reseal the appliance and retest.
If smoke is still not drawn into the
appliance Disconnect the appliance and seek expert advice