19
© Vallox Oy - All rights reserved
MANU
AL
Holding register
Description
R/RW
Datatype
Unit
Range
Default
Notes
1001
Control mode
R/W
U8
0: Constant speed
1: Constant pressure
2: Constant Flow
0
1002
Constant pressure setpoint low
R/W
I16
Pa
-2500…0 (modbus)
-100
1003
Constant pressure setpoint high
R/W
I16
Pa
-2500…0 (modbus)
-300
1004
Constant flow setpoint low
R/W
I16
l/s
10….5000
100
1005
Constant flow setpoint high
R/W
I16
l/s
10….5000
500
1006
Constant speed setpoint low
R/W
I16
%
0…100
20
1007
Constant speed setpoint high
R/W
I16
%
0…100
100
1008
Outdoor temperature compensation enabled
R/W
U8
0/1
0
1009
K value
R/W
I16
K*10
10…9999
160
1010
Outdoor temp comp enabled
R/W
U8
0/1
0
1011
Outdoor air compensation start
R/W
I16
c
-10…10
5
1012
Outdoor air compensation stop
R/W
I16
c
-30…-10
-20
1013
Outdoor air temperature compensation drop
R/W
I16
%
5….90
30
1014
Ext control mode
R/W
U8
2: 0 - 10V in
1: L/H
0: Modbus
1
1015
Measured pressure value
R
I16
Pa
-6000…6000
1016
Measured flow value
R
I16
l/s
0…5000
1017
Motor RPM value
R
I16
rpm
0…4000
1018
External input 0-10VDC value
R
I16
mV
0…10300
1019
External input 1
R
U8
0/1
1020
External input 2
R
U8
0/1
1021
NTC 1
R
I16
*10 ('c)
1022
NTC 2
R
I16
*10 ('c)
1023
Alarm
R
U8
0…255
Active alarms in
bitfield format.
0 = no alarms
1 = er01
2 = er02
3 = er01 + er02
…...
1024
Status
R
U8
1025
Modbus address
R
U8
1026
MODBUS_BAUD_X100
R
I16
In bauds now:
9600,19200, 38400
19200
1027
Modbus databit
R
U8
8…8
8
1028
Modbus parity
R
U8
0: none
1: even
2: odd
1
1029
Modbus stop bits
R
U8
1….2
1
1030
PID P-value
R/W
I16
2…9999
20
1031
PID I-value
R/W
I16
5….90
5
1032
Fan status mode
R/W
U8
0: Tacho
1: Status relay
1
1033
Modbus control state
R/W
U8
0: Off
1: L
2: H
0
MODBUS REGISTERS