Valent VX Series Controller
50
VARIABLE
DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
BACNET
MODBUS
OBJECT
INSTANCE
OBJECT
TYPE
ACCESS
HYST
INDEX
REGISTER
TYPE
SIZE
Compressor_4_
Enable_Digital_Output
Compressor 4 Enable
Digital Output
Active
Inactive
114
BV
ReadCOV_
NoWrite
0
10167
Discrete
Condenser_Fan_1_
Digital_Output
Condenser Fan 1 Digital
Output
Active
Inactive
119
BV
ReadCOV_
NoWrite
0
10172
Discrete
Condenser_Fan_2_
Digital_Output
Condenser Fan 2 Digital
Output
Active
Inactive
120
BV
ReadCOV_
NoWrite
0
10173
Discrete
Condenser_Fan_3_
Digital_Output
Condenser Fan 3 Digital
Output
Active
Inactive
121
BV
ReadCOV_
NoWrite
0
10174
Discrete
Exhaust_Fan_1_Start_
Stop_Digital_Output
Exhaust Fan 1 Start Stop
Digital Output
Active
Inactive
127
BV
ReadCOV_
NoWrite
0
10180
Discrete
Furnace_1_Stage_1_
Digital_Output
Furnace 1 Stage 1 Digital
Output
Active
Inactive
131
BV
ReadCOV_
NoWrite
0
10184
Discrete
Furnace_2_Stage_1_
Digital_Output
Furnace 2 Stage 1 Digital
Output
Active
Inactive
133
BV
ReadCOV_
NoWrite
0
10186
Discrete
Heat_Wheel_Enable_
Digital_Output
Heat Wheel Enable Digital
Output
Active
Inactive
163
BV
ReadCOV_
NoWrite
0
10208
Discrete
PreHeat_Enable_
Digital_Output
PreHeat Enable Digital
Output
Active
Inactive
166
BV
ReadCOV_
NoWrite
0
10211
Discrete
Supply_Fan_1_Start_
Stop_Digital_Output
Supply Fan 1 Start Stop
Digital Output
Active
Inactive
186
BV
ReadCOV_
NoWrite
0
10231
Discrete
BMS_Offline_Alarm.
Active
BMS Offline Alarm
(0=Normal 1=Alarm)
Alarm
Normal
313
BV
ReadCOV_
NoWrite
0
10264
Discrete
Circuit_A_Discharge_
Pressure_Analog_
Input_Alarm.Active
Circuit A Discharge
Pressure Analog Input
Alarm
Alarm
Normal
315
BV
ReadCOV_
NoWrite
10266
Discrete
Circuit_A_Discharge_
Temp_Analog_Input_
Alarm.Active
Circuit A Discharge Temp
Analog Input Alarm
Alarm
Normal
316
BV
ReadCOV_
NoWrite
10267
Discrete
Circuit_A_Suction_
Pressure_Analog_
Input_Alarm.Active
Circuit A Suction Pressure
Analog Input Alarm
Alarm
Normal
319
BV
ReadCOV_
NoWrite
10270
Discrete
Circuit_A_Suction_
Temp_Analog_Input_
Alarm.Active
Circuit A Suction Temp
Analog Input Alarm
Alarm
Normal
320
BV
ReadCOV_
NoWrite
10271
Discrete
Circuit_B_Discharge_
Pressure_Analog_
Input_Alarm.Active
Circuit B Discharge
Pressure Analog Input
Alarm
Alarm
Normal
324
BV
ReadCOV_
NoWrite
10275
Discrete
Cold_Coil_1_
Temperature_Sensor_
Alarm.Active
Cold Coil 1 Temperature
Sensor Alarm (0=Normal
1=Alarm)
Alarm
Normal
387
BV
ReadCOV_
NoWrite
0
10338
Discrete
Comp_Maintenance_
Alarm.Active
Comp Maintenance Alarm
(0=Normal 1=Alarm)
Alarm
Normal
411
BV
ReadCOV_
NoWrite
0
10362
Discrete
Exhaust_Fan_1_Alarm.
Active
Exhaust Fan 1 Alarm
(0=Normal 1=Alarm)
Alarm
Normal
423
BV
ReadCOV_
NoWrite
0
10373
Discrete
Expansion_Board_1_
Alarm.Active
Expansion Board 1 Alarm
(0=Normal 1=Alarm)
Alarm
Normal
434
BV
ReadCOV_
NoWrite
0
10384
Discrete
Expansion_Board_2_
Alarm.Active
Expansion Board 2 Alarm
(0=Normal 1=Alarm)
Alarm
Normal
435
BV
ReadCOV_
NoWrite
0
10385
Discrete
Expansion_Board_3_
Alarm.Active
Expansion Board 3 Alarm
(0=Normal 1=Alarm)
Alarm
Normal
436
BV
ReadCOV_
NoWrite
0
10386
Discrete
Internal_Board_Temp_
Alarm.Active
Internal Board Temp Alarm
(0=Normal 1=Alarm)
Alarm
Normal
498
BV
ReadCOV_
NoWrite
0
10448
Discrete
Multi_Channel_Conf_
Alarm.Active
Multi Channel Conf Alarm
(0=Normal 1=Alarm)
Alarm
Normal
503
BV
ReadCOV_
NoWrite
0
10453
Discrete
Outside_Air_
Temperature_Sensor_
Alarm.Active
Outside Air Temperature
Sensor Alarm (0=Normal
1=Alarm)
Alarm
Normal
507
BV
ReadCOV_
NoWrite
0
10457
Discrete
Outside_Filter_Alarm.
Active
Outside Filter Alarm
(0=Normal 1=Alarm)
Alarm
Normal
508
BV
ReadCOV_
NoWrite
0
10458
Discrete
Outside_RH_Sensor_
Alarm.Active
Outside RH Sensor Alarm
(0=Normal 1=Alarm)
Alarm
Normal
509
BV
ReadCOV_
NoWrite
0
10459
Discrete
Space_CO2_1_
Analog_Input_Alarm.
Active
Space CO2 1 Analog Input
Alarm (0=Normal 1=Alarm)
Alarm
Normal
535
BV
ReadCOV_
NoWrite
0
10485
Discrete
Space_High_Static_
Alarm.Active
Space High Static Alarm
(0=Normal 1=Alarm)
Alarm
Normal
537
BV
ReadCOV_
NoWrite
0
10487
Discrete
Appendix E: Points List