valent VX Series Reference Manual Download Page 5

Valent VX Series Controller

5

setpoint. When a modulating compressor is installed 
(Digital or Inverter Scroll), the compressor modulates 
to maintain the supply air setpoint. Mechanical 
cooling is available in the following configurations: 

   -   

Packaged DX:

 Unit with compressors and 

condensing section located within the same unit. 
this unit may have lead standard, lead digital 
scroll, or lead inverter scroll compressors.

   -   

Split DX:

 Unit with compressors located in the 

unit and utilizes a remote condenser section. 
This type of unit may have lead standard, or lead 
digital scroll compressors. 

Air Source Heat Pump

When a unit is configured as an ASHP, compressors are 
used for cooling and heat pump heating. A reversing 
valve is energized when the unit is in heating mode to 
reverse the flow of the refrigerant. The ASHP is only 
available as a packaged unit with an inverter scroll as 
the lead compressor. 
  •  

Cooling:

 Mechanical cooling operates the same as 

any other unit with compressors by controlling the 
compressors to maintain the supply air temperature 
set point in cooling mode and to maintain the cooling 
coil temperature in dehumidification mode.

  •  

Heat Pump Heating

:

 When heat is required, the 

reversing valve is switched, and the compressors 
are staged to maintain the supply air temperature set 
point. 

  •  

Heat Pump Heating Lockout:

 Heat pump heating 

may be locked out for any of the following reasons:

   -   Defrost is initiated 3 times in one hour.
   -   Supply Air temperature is 5ºF below set point 

for more than 10 minutes and secondary heat is 
available as backup only.

   -   Outside ambient temperature is below the HP 

ambient lockout set point(10ºF).

  •  

Resetting HP Heating Lockout

:

 One of the 

following conditions must occur to return to HP 
heating:

   -   The outside temperature increases by 5ºF.
   -   The outside humidity decreases by 20%RH, if 

humidity sensor is installed.

   -   The unit has been locked out for more than 2 

hours when a humidity sensor is not installed and 
not locked out on low ambient condition.

  •  

Defrost:

 Periodically, the ASHP need to initiate a 

defrost cycle to remove accumulated frost from the 
outside coil when operating in heating mode. The 
saturated suction temperature, the outside ambient 
temperature and/or the outside humidity determine 
when a defrost initiates and terminates.

    

Initiation:

 One of the following must be true for a 

defrost cycle to initiate:

   -   The saturated suction temperature is less than 

-15ºF; or

   -   The saturated suction temperature is less than 

ambient conditions (temp/dewpoint) minus an 
offset (35ºF/25ºF).

    

Termination:

 The defrost cycle is terminated when 

one of the following occur:

   -   The saturated discharge temperatures of all 

refrigerant circuits are greater than the cancel 
defrost set point (80ºF); or

   -   The max defrost time (5 min) has been exceeded.
  •  

Outside Coil Fan Control:

 Refrigerant pressure 

control with outside coil fans will have lead EC fans 
and utilize refrigerant transducers to stage fans 
on and off in cooling and heating. The following 
sequences are based on the current mode of 
operation:

   -   

Cooling/Dehumidification:

 The lead outside fan 

turns on with the first compressor and holds for a 
min of 30 seconds based on the OA temperature. 
The lead fan modulates to maintain the refrigerant 
pressure control set point for cooling mode. Each 
additional outside fan stage turns on based on 
the saturated temperature reaching set point plus 
an offset and turns off when the temperature falls 
below set point after a delay.

   -   

Heating:

 The lead outside fan turns on with 

the first compressor. The lead fan modulates 
to maintain the refrigerant pressure control set 
point for heating mode. Each additional outside 
fan stage turns on based on the saturated 
temperature being below set point minus an 
offset and turns off when the temperature rises 
above set point after a delay.

    - 

  

Defrost:

 When defrost is initiated, the outside 

fans turn off allowing the heat to build and defrost 
the outside coil. When defrost is terminated, the 
outside fans turn on to bring the pressure down 
before switching back to heating mode.

  •  

Secondary Heat:

 A secondary heating device may 

be installed in the unit. This device may be electric 
heat, gas furnace, or a hot water coil. The following 
sequences are available for secondary heat:

   -   

Backup

: Secondary heat only operates when 

heat pump heating is not available.

    - 

  

Supplemental

: Secondary heat will operate 

simultaneously with heat pump heating when the 
compressors are not producing enough heat to 
stay within 2ºF of set point.

Sequence of Operation

Summary of Contents for VX Series

Page 1: ...arm up and cool down capability for improved comfort at the time of occupancy Alarm Management The microprocessor controller will monitor the unit s status for alarm conditions Upon detecting an alarm...

Page 2: ...trol Variables Temp Control 19 21 Dehumidification 22 23 Refrigeration 24 Damper Control 24 25 Energy Recovery 26 Fan Control 27 28 Occupancy 29 Advanced 30 36 Alarms 37 Appendix A Remote Display 38 B...

Page 3: ...following occurs during a soft shutdown Tempering outputs immediately revert back to their off value while Dampers remain open and fans continue to run until The supply air temperature falls below th...

Page 4: ...pied cooling set point Unoccupied Dehumidification If equipped with cooling the unit is enabled when the space relative humidity exceeds the unoccupied space relative humidity set point plus different...

Page 5: ...suction temperature the outside ambient temperature and or the outside humidity determine when a defrost initiates and terminates Initiation One of the following must be true for a defrost cycle to i...

Page 6: ...nd the supply fan speed The following sequences are selectable for supply fan control The fan speed in constrained by its min and max speed set points Constant Volume Supply fan operates at a constant...

Page 7: ...air stream Modulate Wheel When economizer mode is enabled and there is a call for cooling the controller Sequence of Operation modulates wheel speed to maintain the supply temperature set point Energy...

Page 8: ...24VAC for Analog Outputs Outdoor Relative Humidity Sensor Duct Pressure Sensor Building Pressure Sensor Room RH After Cold Coil Temperature Sensor CO2 Sensor Sensor U1 U2 U3 Common Supply Discharge Te...

Page 9: ...Supply Discharge Air Temperature Sensor B1 B2 B3 Commons After Cold Coil Temperature Sensor Outdoor Air Temperature Sensor 24VAC to Controller Staged Compressor 1 24 VAC When Unit On Staged Compresso...

Page 10: ...Heating Output Exhaust Fan VFD Output Energy Recovery Output Space Temperature Mixed Air Temperature Exhaust Air Temperature Space Humidity Space Static Pressure Supply Air Duct Static Pressure Wheel...

Page 11: ...dress Switches 24 VAC High Speed Fan 24 VAC Ignition Controller pCOe High Turndown Furnace Low Speed Pressure Switch Main Gas Valve Small Manifold Main Gas Valve Large Manifold Ignition Controller Ala...

Page 12: ...ess after entering a variable to decrease the current value Unit display on web interface only These two buttons on the virtual keypad display are used to simulate two button actions on the handheld k...

Page 13: ...service access criteria 9998 Once proper login is established the user can view configured input output points associated with the unit controller Pop Up Tools Live Trend User can see current values f...

Page 14: ...on Static pressure Refrigeration Compressor Control Reset History Pressure Control Clear History Heat Pump Control Export History Damper Control Energy Recovery Fan Control Supply Fan Control Exhaust...

Page 15: ...verrides Active Expansion Offline Input Output Status Displays real time conditions from sensors located in the unit and building space if equipped with space mounted sensors Controller output conditi...

Page 16: ...een is active when supply temp control is selected or the active mode of control Displays current supply temperature and supply temperature set point to be achieved Economizer Ramp The economizer ramp...

Page 17: ...n inverter scroll compressor and electronic expansion valve ExV The screen displays information from the EVD electronic valve driver including the number of steps stp of the valve the open percentage...

Page 18: ...pressure control Status points include controller output ramp static pressure in the space and the space static pressure set point Similar status screen will appear for the exhaust fan if the unit is...

Page 19: ...harge set point is a constant value e g 72 F Reference Temperature Set point screen for set point adjustment Space Reset The controller will reset the supply air temperature set point to maintain the...

Page 20: ...The heat cool deadband allows for separate cooling and heating set points when the reset control mode is set for space reset or return air reset Supply Set Points Cooling and heating supply set points...

Page 21: ...g Example If set point 60 F unoccupied heating is enabled when space temperature equals 60 F and below Unoccupied heating is disabled when space temperature is above 65 F Menu Winter Ramp The winter r...

Page 22: ...et points can be adjusted over the BMS Dehumidification Mode Unoccupied If the unit is unoccupied while there is a dehumidification call the unit will start and dehumidify until the unoccupied dehumid...

Page 23: ...F offset c Overcooled If space or return reset is enabled the target is considered over cooled when it is 4 F below set point for 5 minutes It remains overcooled until the target is at set point and t...

Page 24: ...recirculation air 100 Full OA Minimum Position When in the occupied mode the active set point will be equal to a local min OA set point which may be constant or reset by fan speed if equipped with a m...

Page 25: ...For example if a unit is equipped with a DCV CO2 and an economizer sequence the OA damper set point will react to an economizer demand even if the CO2 set point is satisfied Likewise if economizer is...

Page 26: ...ry Wheel Jog Function This screen display the energy recovery wheel jog function This screen only appears if the unit has an energy recovery wheel and stop wheel economizer method for control Momentar...

Page 27: ...ure control loop Space Pressure Fan speed is determined by building pressure control loop CO2 Fan speed is determined by CO2 control loop Single Zone VAV The supply fan is modulated in addition to the...

Page 28: ...from the controller to the VFD 25 Speed Min speed 100 Speed Max speed Set Point Selections Constant Volume The fan speed will be constant set from screen e g 100 BMS The BMS can directly control the f...

Page 29: ...s remain in unoccupancy mode Schedule Allows the user to set an occupancy schedule for each individual day of the week Unoccupied Start Enable Modes This screen only appears if unit is provided with u...

Page 30: ...to turn the unit on or off Override Occupancy Control When manual override is set to enable use the arrow buttons to change occupancy control Override the Supply Fan VFD Speed The speed is the propor...

Page 31: ...or This screen only appears if the unit is equipped with DX cooling When manual override is set to enable use the arrow buttons to turn individual compressor requests on or off Override the Modulating...

Page 32: ...s screen will be available when the unit is configured as a heat pump When in manual mode change the demand to control the position of the reversing valve and the amount of compressor request The comp...

Page 33: ...set to BACnet MSTP Factory settings are shown in the screen to the left To change BACnet MSTP parameters 1 Go to Network Settings menu and view BACnet MSTP Config screen 2 Move cursor to desired para...

Page 34: ...have been entered enable the Save Settings option and press the enter button 4 Reboot the controller by cycling power to the unit Allow several minutes for the controller to initialize BMS Watchdog Th...

Page 35: ...The file must be named User_Backup txt 2 Insert the USB drive into the controller s USB port 3 Go to the Main Menu Unit Enable screen Press the Enter and Up or Down arrow buttons to disable the unit 4...

Page 36: ...y login password Consult factory for IO configuration changes ADJUSTMENT OF I O CONFIGURATION MUST ONLY BE DONE UNDER FACTORY GUIDANCE IMPROPER ADJUSTMENT MAY RESULT IN SYSTEM DAMAGE Control Variables...

Page 37: ...ler Alarm only Pressure switch closed with combustion fan off Indicates low pressure switch was closed with no call for combustion fan Alarm only Combustion fan not proved Indicates a call for low spe...

Page 38: ...Type Backlit LED with lighted buttons Installation The remote display connects to the unit mounted controller through a six wire RJ25 or RJ12 telephone cable straight When ordered from the factory a...

Page 39: ...Outputs Configuring the I O Type In order to edit and configure the I O configuration of the unit go to Ctrl Variables Advanced I O Configuration The user must enable the Editable option for configuri...

Page 40: ...lso provides the functionality to average up to 4 temperature readings through the microprocessor The space thermostat is shipped loose with installation by others and is a Modbus connected device Roo...

Page 41: ...erating properly Red indicates that there is a problem with the unit Network LED Flashing Red Slowly indicates that there has been no communications for 60 seconds Flashing Green Slowly indicates that...

Page 42: ...of measured airflow Dual airflow probe averaging Modbus connectivity Display and Navigation The LCD screen will by default show the current airflow that is being measured To enter the menu to set up t...

Page 43: ...log_ Input Space Relative Humidity 89 AI ReadCOV_ NoWrite 0 1 30355 Input 2 Space_Static_ Pressure_Analog_Input Space Static Pressure 94 AI ReadCOV_ NoWrite 0 01 30365 Input 2 Supply_Duct_Static_ Pres...

Page 44: ...omizer_Temp_ Enable_Set Point Economizer Ambient Temp Enable Set Point Allow Econ when OAT Spt 16 AV ReadCOV_ Commandable 0 40031 Holding 2 Economizer_Enthalpy_ Enable_Set Point Economizer Enthalpy En...

Page 45: ...Signal_ BMS Allows the BMS to control OAD position True BMS False Local 136 AV ReadCOV_ Commandable 0 1 40089 Holding 2 Outside_Air_Damper_ Minimum_Set Point Outside Air Damper Minimum Set Point 137 A...

Page 46: ...Fan Supply Tracking Ramp 50 AV ReadCOV_ NoWrite 1 30021 Input 2 Head_Pressure_ Control_Ramp_1_ Ramp Head Pressure Control Ramp 1 51 AV ReadCOV_ NoWrite 1 30023 Input 2 Head_Pressure_ Control_Ramp_2_ R...

Page 47: ...rite 0 1 30517 Input 2 Exhaust_Fan_Speed_ Analog_Output Exhaust Fan Speed Analog Output 231 AV ReadCOV_ NoWrite 0 1 30521 Input 2 Hot_Gas_Reheat_ Analog_Output Hot Gas Reheat Analog Output 235 AV Read...

Page 48: ...0 3 Coil BMS_Occupancy_ Command Occupancy Command True Unoccupied False Occupied Unoccupy Occupy 3 BV Read_ Commandable 0 4 Coil Reset_All_Alarms Alarm Reset Command Reset Normal 4 BV Read_ Commandabl...

Page 49: ...ing Active Inactive 28 BV ReadCOV_ NoWrite 0 10014 Discrete Heating_is_On Indicates that the unit is heating Active Inactive 29 BV ReadCOV_ NoWrite 0 10015 Discrete Dehumidification_ Mode_Enabled Indi...

Page 50: ...ure Analog Input Alarm Alarm Normal 319 BV ReadCOV_ NoWrite 10270 Discrete Circuit_A_Suction_ Temp_Analog_Input_ Alarm Active Circuit A Suction Temp Analog Input Alarm Alarm Normal 320 BV ReadCOV_ NoW...

Page 51: ...m Error Alarm 0 Normal 1 Alarm Alarm Normal 567 BV ReadCOV_ NoWrite 0 10517 Discrete Wheel_Rotation_ Alarm Active Wheel Rotation Alarm 0 Normal 1 Alarm Alarm Normal 576 BV ReadCOV_ NoWrite 0 10526 Dis...

Page 52: ...al 617 BV ReadCOV_ NoWrite 0 10567 Discrete Al_SuctHiP_COMP_1 Active Compressor Envelope SuctHiP_COMP 0 Normal 1 Alarm Alarm Normal 618 BV ReadCOV_ NoWrite 0 10568 Discrete Al_SuctLowP_ COMP_1 Active...

Page 53: ...adCOV_ NoWrite 1 30195 Input 2 Large Board Points Binary Values Read Only High_Low_Press_ Circ_A_Alarm Active High Low Pressure Switch Alarm Circuit A Alarm Normal 733 BV ReadCOV_ NoWrite 0 10682 Disc...

Page 54: ...ive 124 BV ReadCOV_ NoWrite 0 10177 Discrete Condenser_Fan_7_ Digital_Output Condenser Fan 7 Digital Output Active Inactive 125 BV ReadCOV_ NoWrite 0 10178 Discrete Comp_Circ_A_High_ Pressure_Alarm Ac...

Page 55: ...FURNACE CONTROL CENTER OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL ROOM THERMOSTAT 1 ROOM THERMOSTAT 2 ROOM THERMOSTAT 3 ROOM THERMOSTAT 4 OPTIONAL OPTIONAL OPTIONAL OPTIONAL SHIELDED NETB GND PWR N...

Page 56: ...ics that shipped with your unit They can typically be found attached to the main control panel door Mechanical and Controls Manuals Find current mechanical and controls manuals here www valentair com...

Reviews: