Valent VX Series Controller
20
T
emperaTure
s
eT
p
oinT
This screen only appears if supply temp control, space reset, or return reset is
selected as the reset control mode.
Set Point Selections:
Local
– The space set point will be constant; set from screen (e.g. 72°F).
BMS
– The BMS can directly control the space temperature set point (requires
BMS communication option).
T-Stat
– The space set point will be adjustable from the space thermostat.
Reference Appendix: Room Thermostat Quick Start for additional information.
h
eaT
c
ool
d
eadband
This screen only appears if space reset or return air reset is selected as the reset
control mode. The heat cool deadband allows for separate cooling and heating
set points when the reset control mode is set for space reset or return air reset.
s
upply
s
eT
p
oinTs
Cooling and heating supply set points screens only appear if outdoor reset, space
reset, or return air reset is selected. These screens allow the user to set the min
and max set point limits for cooling or heating operation. The controller will adjust
the supply temperature set point between the set limits depending on mode of
operation.
m
ode
s
wiTch
d
isplay
This screen displays the delay time required before switching between heating
and cooling mode.
s
TarTup
d
isplay
This screen displays the delay time after the fans have started and tempering
begins
Menu
o
uTside
s
eT
p
oinTs
This screen only appears if outside reset is selected as the reset control mode.