![valent VX Series Reference Manual Download Page 43](http://html2.mh-extra.com/html/valent/vx-series/vx-series_reference-manual_3196442043.webp)
Valent VX Series Controller
43
VARIABLE
DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
BACNET
MODBUS
OBJECT
INSTANCE
OBJECT
TYPE
ACCESS
HYST
INDEX
REGISTER
TYPE
SIZE
Analog Inputs - Read Only
Circuit_A_Discharge_
Temp_Analog_Input
Circuit A Discharge
Temperature
1
AI
ReadCOV_
NoWrite
0.1
30195
Input
2
Circuit_A_Suction_
Temp_Analog_Input
Circuit A Suction
Temperature
3
AI
ReadCOV_
NoWrite
0.1
30199
Input
2
Cold_Coil_1_Temp_
Analog_Input
Cold Coil 1 Temperature
25
AI
ReadCOV_
NoWrite
0.1
30243
Input
2
CL_Coil_Spt_Temp
Controls Lite Cooling Coil
Set Point Temperature
value
31
AI
ReadCOV_
NoWrite
0.1
30255
Input
2
CL_Supply_Spt_Temp
Controls Lite Supply Set
Point Temperature value
32
AI
ReadCOV_
NoWrite
0.1
30257
Input
2
Outside_Air_Temp_
Analog_Input
Outside Air Temperature
37
AI
ReadCOV_
NoWrite
0.1
30267
Input
2
Space_Temp_Analog_
Input
Space Temperature
44
AI
ReadCOV_
NoWrite
0.1
30281
Input
2
Supply_Temp_Analog_
Input
Supply Temperature
45
AI
ReadCOV_
NoWrite
0.1
30283
Input
2
Outside_RH_Analog_
Input
Outside % Relative
Humidity
86
AI
ReadCOV_
NoWrite
0.1
30349
Input
2
Space_RH_Analog_
Input
Space % Relative Humidity
89
AI
ReadCOV_
NoWrite
0.1
30355
Input
2
Space_Static_
Pressure_Analog_Input
Space Static Pressure
94
AI
ReadCOV_
NoWrite
0.01
30365
Input
2
Supply_Duct_Static_
Pressure_Analog_Input Supply Duct Static Pressure
95
AI
ReadCOV_
NoWrite
0.01
30367
Input
2
Space_CO2_1_
Analog_Input
Space 1 CO2 ppm
116
AI
ReadCOV_
NoWrite
10
30401
Input
2
Circuit_A_Discharge_
Pressure_Analog_Input
Circuit A Discharge
Pressure
119
AI
ReadCOV_
NoWrite
0.1
30407
Input
2
Circuit_A_Suction_
Pressure_Analog_Input Circuit A Suction Pressure
120
AI
ReadCOV_
NoWrite
0.1
30409
Input
2
Circuit_B_Discharge_
Pressure_Analog_Input
Circuit B Discharge
Pressure
121
AI
ReadCOV_
NoWrite
1
30411
Input
2
Aux_In_Customer_1
Customer defined auxiliary
input
640
AI
ReadCOV_
NoWrite
0.1
30639
Input
2
Aux_In_Customer_2
Customer defined auxiliary
input
642
AI
ReadCOV_
NoWrite
0.1
30641
Input
2
Aux_In_Customer_3
Customer defined auxiliary
input
644
AI
ReadCOV_
NoWrite
0.1
30643
Input
2
Aux_In_Customer_4
Customer defined auxiliary
input
646
AI
ReadCOV_
NoWrite
0.1
30645
Input
2
Aux_In_Customer_5
Customer defined auxiliary
input
648
AI
ReadCOV_
NoWrite
0.1
30647
Input
2
Aux_In_Customer_6
Customer defined auxiliary
input
650
AI
ReadCOV_
NoWrite
0.1
30649
Input
2
Appendix E: Points List