Valent VX Series Controller
33
c
.
p
co b
oard
a
ddress
This screen will appear with or without a network protocol provided with the unit.
This screen allows the user to configure the IP setting for BMS and/or when
the Web User Interface will be utilized. The controller may have a DHCP server-
assigned address or a manually-assigned static IP address. Factory settings are
shown in the screen to the left.
The Network Settings Menus allows the user to view and modify network
settings. The
service password (9998)
is required to make changes.
Control Variables
Advanced
Network Settings
c
onTroller
bac
neT
ip c
onFig
This screen will appear if the unit is set for BACnet IP and allows the user to set
the device and port settings.
bac
neT
msTp p
arameTers
This screen only appears if the selected BMS protocol is set to BACnet MSTP.
Factory settings are shown in the screen to the left.
To change BACnet MSTP parameters:
1. Go to Network Settings menu and view BACnet MSTP Config screen.
2. Move cursor to desired parameter by pressing the enter button. Press up and
down arrows to adjust the parameter. Press enter to accept adjusted value.
3. Once desired parameters have been entered, enable the ‘Save Settings’
option and press the enter button.
4. Reboot the controller by cycling power to the unit. Allow several minutes for
the controller to initialize.
Menu
m
odbus
Tcp s
lave
.
This screen will appear if the unit is set for Modbus TCP and
allows the user to set device ID number.
v
iew
and
c
hange
The
u
noccupied
u
niT
o
peraTion
.
Possible unoccupied unit operation methods include:
• Unit Off
• Night Setback Cycle
• Recirculation with Unoccupied Set Points
• Normal Operation with Unoccupied Set Points
e
nable
m
orning
w
arm
u
p
and
c
ool
d
own
.
The user can enable morning warm up, morning cool down, and set the duration
for the sequence.