Valent VX Series Controller
48
VARIABLE
DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
BACNET
MODBUS
OBJECT
INSTANCE
OBJECT
TYPE
ACCESS
HYST
INDEX
REGISTER
TYPE
SIZE
Binary Inputs - Read Only
Exhaust_Fan_1_
Status_Digital_Input
Exhaust Fan 1 Status
Active
Inactive
23
BI
ReadCOV_
NoWrite
0
24
Discrete
Occupancy_Digital_
Input
Occupancy Digital Input
Status
Active
Inactive
53
BI
ReadCOV_
NoWrite
0
54
Discrete
Outside_Filter_Alarm_
Digital_Input
Outside Filter Alarm Digital
Input Status
Active
Inactive
54
BI
ReadCOV_
NoWrite
0
55
Discrete
Shutdown_Alarm_
Digital_Input
Shutdown Alarm Digital
Input Status
Active
Inactive
75
BI
ReadCOV_
NoWrite
0
76
Discrete
Supply_Fan_1_Status_
Digital_Input
Supply Fan 1 Status
Active
Inactive
78
BI
ReadCOV_
NoWrite
0
79
Discrete
Unit_Enable_Digital_
Input
Remote Unit Enable Digital
Input Status
Active
Inactive
82
BI
ReadCOV_
NoWrite
0
83
Discrete
Wheel_Status_Digital_
Input
Heat Wheel Status
Active
Inactive
83
BI
ReadCOV_
NoWrite
0
84
Discrete
Binary Values - Read/Write - Commandable
BMS_Watchdog
BMS Watchdog command.
Used to determine comm
status. Must heartbeat
within the watchdog
timeout delay to detect
comm status.
Active
Inactive
1
BV
Read_
Commandable
0
2
Coil
System_Enable
Master system enable/
disable point.
Enable
Disable
2
BV
Read_
Commandable
0
3
Coil
BMS_Occupancy_
Command
Occupancy Command. True
= Unoccupied. False =
Occupied.
Unoccupy
Occupy
3
BV
Read_
Commandable
0
4
Coil
Reset_All_Alarms
Alarm Reset Command.
Reset
Normal
4
BV
Read_
Commandable
0
5
Coil
Outside_RH_Source_
BMS
Outside RH Source
Selection. True = BMS.
False = Local.
BMS
Local
5
BV
Read_
Commandable
0
6
Coil
Outside_Temp_
Source_BMS
Outside Temp Source
Selection. True = BMS.
False = Local.
BMS
Local
6
BV
Read_
Commandable
0
7
Coil
Return_RH_Source_
BMS
Return RH Source
BMS
Local
7
BV
Read_
Commandable
8
Coil
Return_Temp_Source_
BMS
Return Temp Source
BMS
Local
8
BV
Read_
Commandable
9
Coil
Space_1_CO2_
Source_BMS
Space 1 CO2 Source
Selection. True = BMS.
False = Local.
BMS
Local
9
BV
Read_
Commandable
0
10
Coil
Space_RH_Source_
BMS
Space RH Source Selection.
True = BMS. False = Local.
BMS
Local
12
BV
Read_
Commandable
0
13
Coil
Space_Static_Source_
BMS
Space Static Source
Selection. True = BMS.
False = Local.
BMS
Local
13
BV
Read_
Commandable
0
14
Coil
Space_Temp_Source_
BMS
Space Temp Source
Selection. True = BMS.
False = Local.
BMS
Local
14
BV
Read_
Commandable
0
15
Coil
SF_Control_Source_
BMS
Allows the BMS to control
supply fan speed. True =
BMS. False = Local.
BMS
Local
56
BV
Read_
Commandable
0
19
Coil
EF_Control_Source_
BMS
Allows the BMS to control
exhaust fan speed. True =
BMS. False = Local.
BMS
Local
57
BV
Read_
Commandable
0
20
Coil
OAD_Control_Source_
BMS
Allows the BMS to control
OAD position. True = BMS.
False = Local.
BMS
Local
59
BV
Read_
Commandable
0
22
Coil
Appendix E: Points List