Only when expanding the analog terminal block installation on a DIN rail:
Reconnect the 24 VDC power cable connector (disconnected in
) in the power
block.
17. Reconnect power in the cabinet.
a. Switch on the circuit breaker.
b. Switch on mains power.
For instructions on configuring measurement units and scaling in DL4000 data loggers,
see
Vaisala viewLinc Enterprise Server Version 5.0 User Guide
(M211975EN).
More information
‣
CAB100B wiring diagrams (page 126)
‣
CAB100B layout diagrams (page 135)
6.3.1 Analog input channel wiring of loop-powered
measurement devices
• Small screwdriver
• Cable cutters
• Cable-stripping pliers
CAB100 analog input channels are not surge protected. Therefore, note the
following:
• The analog input channel wiring must not exceed 30 meters.
• The wiring must not come from outside the building where CAB100 is installed.
If CAB100 cannot be installed in an environment that meets the above criteria, use a
suitable surge protection device that has been installed following local regulations.
CAUTION!
CAB100 Installation Guide
M212242EN-B