5
Installation instructions VRC 430f 0020042470_01
4 Assembly
The VRC 430f must be installed on a wall in the living
area.
The VRC 430f is supplied with the following
radio outdoor sensors:
– VR 20
– VR 21 (with integrated DCF 77 RF time signal receiver)
Energy is supplied to both wireless outdoor sensors via
a solar cell.
Appliance
Article no.
Controller
VR 20
VR 21
VRC 430f
0020028521
0020028522
1
0020028523
0020028524
0020028525
1
VRC 430f
0020028526
1
Table 4.1 VRC 430f with radio outdoor sensor
4.1 Scope
of
delivery
Check the scope of delivery against Table 4.2.
Pos. number Component
1
1
Controller VRC 430f
2
1
Radio outdoor sensor VR 20
or wireless outdoor sensor VR 21 (DCF)
3
2
Fixing equipment
4
1
6-pin edge connector
(only required for the installation of a hy-
draulic switch; e.g. in combination with mixer
module VR 61)
5
1
Radio receiver unit
6
1
Wall socket for radio receiver unit
7
1
Battery set (4x AA)
8
1
Operating and
Installation Manual
Table 4.2 VRC 430f scope of supply
4.2 Accessories
The following accessories can be installed in addition to
the VRC 430f weather compensator:
2 from 7 multi-functional module
The VRC 430f can control a circulation pump via the
multifunctional model 2 of 7.
Mixer module VR 61
The VR 61 mixer module expands the VRC 430f so it has
the functionality of a dual circuit controller.
Solar module VR 68
The VR 68 solar module can be used by the VRC 430f
to control a solar installation.
h
Note!
If the VRC 430f is connected to additional
components, please observe all instructions in
relation to those components.
4.3 Installating
the
unit
Only install the controller and the radio receiver unit
in dry rooms.
The controller should be fitted so as to ensure prob-
lem-free measurement of the room temperature;
e.g. on a room wall of the main living room at a
height of approx. 1.5 m.
Before you install the controller and wireless out-
door sensor, check the intended locations for possi-
ble functional impairment of the radio signal path by
electrical devices or building components. If inter-
ference in the signal path is likely, an alternative in-
stallation location must be found.
If the switch-on room temp. is activated, advise the
user that, in the room where the controller is
mounted, all the radiator valves must be fully open.
See Section 4.5 for the mounting location of the wire-
less outdoor sensor.
4.4
Installing the wireles transmitter in the
heating unit
e
Danger!
Live connections!
When working on the unit's control cabinet
there is a danger to life by electric shock.
Switch the power supply off before working on
the control cabinet and secure against re-con-
nection.
Open the control cabinet only when the appli-
ance is disconnected from the power source.
Proceed as follows:
Switch off the appliance.
Turn off the power supply to the appliance and se-
cure the power supply to prevent it from being unin-
tentionally switched back on.
Remove the front panel on the appliance and re-
move the cover plate on the control cabinet.
Push the radio receiver unit into the plug connec-
tion provided in the control cabinet using your plug
connector.
Re-connect the power supply to the appliance.
Switch the appliance on.
Assembly 4
Summary of Contents for VRC 430f
Page 2: ......
Page 40: ...0020042470_01 GB 092008 ...