background image

Installation 5

uniSTOR GB

15

The Vaillant uniSTOR is provided with an external
expansion vessel.

Connect the expansion vessel to the installed water
controls by either:
i.  Screwing the vessel directly into the control assem-

bly at the purpose provided connection (1, fig. 8) or,

ii. Connecting the vessel to the control assembly via 

copper pipe or a suitable approved flexible connec-
tion hose (4, fig. 8), ensuring that the vessel is
adequately supported.
Use the supplied Expansion Vessel Mounting
Bracket for wall installation.

Connect the balanced pressure cold water supply (if
required) to the cold water control pack (see fig. 8).

Note:
In areas where the mains water pressure is high
(4 bar or above) the cold water supply to a bath
or shower mixer valve can be taken from the
balanced pressure cold water outlet (5, fig. 8) of
the cold water controls. This will ensure that
both hot and cold supplies to the mixer valve
are at approximately the same pressure. The
cold water supply for all other terminal fittings
should be teed into the cold water supply
pipework to the uniSTOR upstream of the cold
water controls.

Connect the DHW outlet pipework to the 22 mm
domestic hot water outlet on the uniSTOR.
Continue with 22 mm size pipe to the first tee fitting
after which 15 mm pipework should be adequate.
If the pipe runs are of excessive length or there are
several terminal fittings supplied, extend the length of
pipework in 22 mm.

Connect the secondary return if required as shown in
4.2: Secondary Return.

5.4.3 Safety valve discharge pipework

Connect the temperature/pressure relief and
expansion relief valves to the tundish using 15 mm
pipe and install the discharge pipework from the
tundish in accordance with section 5.1.4: Discharge
Pipework.

5.4.4 Drain Valve

The drain valve supplied with the uniSTOR has to be
fitted in the cold water mains supply between the
uniSTOR cylinder and the cold water control valves as
low as possible (see fig. 6)
We recommand to fit a hose pipe in the outlet of the
drain valve approximately 1 meter below the bottom of
the cylinder (this can be achieved by connecting a
suction hose to the outlet of the drain valve).

Fig. 8a

40

40

8 bar*

4 bar*

3 bar*
2 bar*

1 bar*

8 bar*

4 bar*
3 bar*

2 bar*

1 bar*

30

30

20

20

flow available (litres/min) at entry to system

Mixed water @ 40 

°

C, mixed from

 

60 % hot water @ 60 

°

C and

 

40 % cold water @ 10 

°

C

Notes:
1) flow rates shown apply to situations where the supply is capable of supplying an adequate dynamic pressure.

3) where static water pressures are less than 1 bar, consult Vaillant Ltd.

* static supply pressure of incoming water supply.

flow out (litres/min) of the system

10

10

0

40

40

30

30

20

20

flow available (litres/min) at entry to system

flow out (litres/min) of the system

10

10

0

Flow rates from uniSTOR, hot 60 

°

C.

Flow rates from uniSTOR, hot cold mixed.

0020005468_02_GB_042008.qxd  16.04.2008  14:17 Uhr  Seite 15

Summary of Contents for uniSTOR VIH GB SERIES

Page 1: ...Instructions for Installation and Use uniSTOR Unvented hot water storage cylinder VIH GB 125 S VIH GB 155 S VIH GB 180 S VIH GB 210 S VIH GB 260 S VIH GB 310 S GB...

Page 2: ...y System 8 4 2 Secondary Return 8 5 Installation 9 5 1 Installation requirements 9 5 1 1 Siting 9 5 1 2 Mains Water Pressure 9 5 1 3 Pipework Primary Circuit 9 5 1 4 Discharge Pipework 9 5 1 4 1 High...

Page 3: ...ting is controlled by a separatly fitted 2 port valve in conjunction with suitable external controls such as a programmer room thermostat or thermostatic radiator valves 1 3 Immersion Heater uniSTOR c...

Page 4: ...28 30 33 39 44 49 kg Weight full 145 175 205 245 310 340 kg Height 969 1179 1339 1499 1789 2109 mm Cylinder connections Cold mains inlet 22 mm compression DHW outlet 22 mm compression Balanced pressu...

Page 5: ...ate cylinder heat up time 15 C to 65 C minutes Reheat time for 70 of cylinder contents minutes 50 40 10 20 30 40 60 50 30 20 12 Heat input to cylinder kW Cylinder Heat Up Times 15 20 25 30 38 35 VIH G...

Page 6: ...d be completed by the installer and or commissioning engineer and handed to the user All CORGI registered installers carry a CORGI ID card and have a registration number Both should be recorded in you...

Page 7: ...y will become invalid if the damage is due to frost or freezing transient voltages lightning strikes or any act of vandalism or misuse 2 The proof of purchase must be produced in the event of any warr...

Page 8: ...aws of the local Water Undertaking The installation is subject to Building Regulation approval notify the Local Authority of intention to install In the event of parts replacement use only genuine spa...

Page 9: ...uniSTOR unvented storage cylinder should not be installed Contact Vaillant Ltd for details on alternative hot water supply systems In order to minimise frictional losses minimum 22 mm bore is recomme...

Page 10: ...g temperature relief valve 500 mm maximum 300 mm minimum providing that where children may play or otherwise come into contact with discharges a wire cage or similar guard is positioned to prevent co...

Page 11: ...84 314 589 903 VIH GB 180 S 1308 1339 454 384 314 589 1038 VIH GB 210 S 1468 1499 454 384 314 589 1118 VIH GB 260 S 1758 1789 454 384 314 589 1408 1376 VIH GB 310 S 2078 2109 454 384 314 589 1648 1376...

Page 12: ...niSTOR GB 12 1 Boiler 2 uniSTOR cylinder 3 2 port motorised valve provided with the boiler 4 Immersion heater 5 2 port motorised valve A Boiler flow B Boiler return Fig 5 1 A B 2 4 3 5 M M DHW 5 3 Fun...

Page 13: ...f valve 2 Expansion relief valve 3 Pressure limiting valve combined with strainer 4 Connection to expansion vessel 5 Balanced pressure cold water outlet 6 Cold water mains inlet 7 DHW outlet 8 Tundish...

Page 14: ...ns supply to the uniSTOR To ensure optimum performance from the uniSTOR and particularly in installations where the balanced pressure cold water outlet 5 fig 8 is to be used the pipework provided from...

Page 15: ...pe runs are of excessive length or there are several terminal fittings supplied extend the length of pipework in 22 mm Connect the secondary return if required as shown in 4 2 Secondary Return 5 4 3 S...

Page 16: ...ls 1 Thermostat adjustable b Immersion heater 2 Thermal cut out with Reset button 3 Sensor 2 1 2 a b 1 3 230 V AC 3 kW 1 2 3 N L Important The immersion heater incorporates an energy cut off device an...

Page 17: ...for electrical installations IEE Wiring Regulations 16th edition Check that the sensors from the immersion heater and the cylinder are positioned correctly in the tubes Note A special accessory is off...

Page 18: ...Note Earth not required Link L 2 5 Siemens Landis Staefa RWB2 RWB9 Potterton Myson EP 2002 EP 3002 EP 6002 Note Link L 5 Sunvic Select 207 N L 2 3 4 5 3 7 6 1 E N L 2 3 4 1 E N L 2 3 4 5 3 7 6 1 N 3 5...

Page 19: ...4 5 6 7 8 9 10 SL 1 2 3 uniSTOR VIH GB Central Heating 2 Port Motorised Valve Hot Water 2 Port Motorised Valve Cylinder Stat E BL BR GR OR L N Pump E BL BR GR OR L N HW ON CH ON 2 Channel Programmer...

Page 20: ...cylinder has reached temperature and all radiators in the system are hot Then once again drain the complete CH system to remove residues from the pipework and refill and vent again as above Reset the...

Page 21: ...ring frost conditions Advise the user that the immersion heater is provided as a back up means of water heating and is not intended for use at the same time that the boiler is heating the cylinder Fin...

Page 22: ...g to controls instructions Is 2 port valve in correct position DHW position Does cylinder thermostat operate Replace cylinder thermostat Vent heating coil of air H fig 4 Check replace 2 port valve Is...

Page 23: ...ansion vessel Does pressure hold Turn off boiler and immersion heater Is discharge still occuring YES NOT OK Is the discharge occuring only when the cylinder is being heated YES NO Is pressure downstr...

Page 24: ...ty YES Replace TPRV Replace immersion heater NO YES NO Is operation now OK OK Fault remedied NOT OK Check temperature control of boiler Does 2 port valve change to heating position when cylinder reach...

Page 25: ...limiting valve OK Check pressure limiting valve OK Check sytem for blockage OK Symptoms still persisting YES Check system as for discharge from temperature or expansion relief valve Inform customer t...

Page 26: ......

Page 27: ......

Page 28: ...0020005468_02 GB 042008 Subject to alteration Printed in Germany...

Reviews: