8 Fault finding
uniSTOR GB
24
Fig. 17
Water discharging from temperature/
pressure relief valve (TPRV).
Manually reset the TPRV. Is
discharge still occuring?
YES
NO
Is discharge occuring only
when the boiler is in use?
Is discharge occuring only
when the immersion heater
is in use?
Are immersion heater
thermostat and cut out
faulty?
YES
Replace TPRV.
Replace immersion heater.
NO
YES
NO
Is operation now OK?
OK
Fault remedied.
NOT OK
Check temperature control
of boiler.
Does 2-port valve change to
heating position when
cylinder reaches
temperature?
Check operation of
cylinder thermostat and
thermal cut out
YES
OK
NO
Remedy fault
according to boiler
instructions.
NOT
OK
Reset thermal cut out/
Replace cylinder
thermostat.
NOT
OK
Check operation of
2-port valve.
Replace
2-port valve.
NOT
OK
OK
Is discharge still occuring?
OK
NO
YES
NO
Replace TRPV.
YES
Fault C:
0020005468_02_GB_042008.qxd 16.04.2008 14:17 Uhr Seite 24
Summary of Contents for uniSTOR VIH GB SERIES
Page 26: ......
Page 27: ......
Page 28: ...0020005468_02 GB 042008 Subject to alteration Printed in Germany...