Adapting the boiler to the heating installation
Installation and maintenance instructions ecoTEC plus 0020134833_01
53
11
Code
Parameters
Adjustable values
Factory set-
ting
Your own
setting
D.058
Activation of solar post-heating for VUW
boilers;
Switch hot water mode
Solar post-heating mode deactivated
Hot water activation target value minimum 60 °C
Solar post-
heating mode
deactivated
D.060
Number of temperature limiter shut-
downs
Number of shutdowns
Not adjustable
D.061
Number of ignition device cutoffs
Number of unsuccessful ignitions in the last attempt
Not adjustable
D.064
Average ignition time
In seconds
Not adjustable
D.065
Maximum ignition time
In seconds
Not adjustable
D.067
Remaining burner anti-cycling time
In minutes
Not adjustable
D.068
Unsuccessful ignitions at 1st attempt
Number of unsuccessful ignitions
Not adjustable
D.069
Unsuccessful ignitions at 2nd attempt
Number of unsuccessful ignitions
Not adjustable
D.070
Set diverter valve position
Normal operating mode
Mid-position (parallel operation)
Continuous heating adjustment
Normal oper-
ating mode
D.071
Target value maximum heating flow tem-
perature
40 to 80 °C
75 °C
D.072
Internal pump overrun after cylinder
charging
Adjustable from 0 - 10 minutes in increments of 1
minute
2 mins
D.073
Warm start target offset
Adjustable from -15 K to 5 K
0
D.074
actoSTOR Anti-legionella function
OFF, ON
ON
D.075
Max. charging time for domestic hot
water cylinder without independent con-
trol system
20 - 90 min
45 mins
D.076
Device specific number
17 = VUI 937
Not adjustable
D.077
Limit on cylinder charging output
in kW
Limit on cylinder charging output
in kW
D.078
Limit on cylinder charging temperature
in °C
55 °C - 80 °C
Note: The chosen value must be at least 15 K or 15 °C
above the set cylinder target value.
75 °C
D.080
Operating hours, heating
In hours (h)
Not adjustable
D.081
Operating hours, hot water generation
In hours (h)
Not adjustable
D.082
Number of burner start-ups in heating
mode
Number of start-ups
Not adjustable
D.083
Number of burner start-ups in hot water
mode
Number of start-ups
Not adjustable
D.084
Maintenance indicator: Number of hours
until the next maintenance
Setting range: 0 to 3000 hrs and "---" for deactivated
"---"
D.088
Start delay for hot water draw-off detec-
tion via impeller
1.5 l/min and no delay,
3.7 l/min and 2 s delay
1.5 l/min and
no delay
11.1 Diagnostics codes (continued)