Flue gas installation
Installation and maintenance instructions ecoTEC plus 0020134833_01
29
7
Location
Minimum
dimensions
A
Directly below an opening, air brick, opening win-
dows, etc.
300 mm
B Above an opening, air brick, opening window, etc.
300 mm
C
Horizontally to an opening, air brick, opening win-
dow, etc.
300 mm
D
Below temperature-sensitive building components
e.g. plastic gutters, soil pipes or drain pipes
75 mm
E
Below eaves
200 mm
F
Below balconies or car port roof
200 mm
G From a vertical drain pipe or soil pipe
150 mm
H From an internal or external corner
200 mm
I
Above ground, roof or balcony level
300 mm
J
From a surface facing the terminal
600 mm
K From a terminal facing the terminal
1200 mm
L
From an opening in the car port (e.g. door, win-
dow) into the dwelling
1200 mm
M Vertically from a terminal on the same wall
1500 mm
N Horizontally from a terminal on the same wall
300 mm
O From the wall on which the terminal is mounted
0 mm
P From a vertical structure on the roof
N/A
Q Above intersection with roof
300 mm
R
Horizontally to a window or opening on pitched or
flat roofs
600 mm
S
Above a window or opening on pitched or flat
roofs
600 mm
T
Below a window or opening on pitched or flat
roofs
2000 mm
7.1
Position of the termination in a fan-assisted air/flue gas
duct
BS 5440–1 It is recommended that the fanned flue terminal
should be positioned as follows:
a)
at least 2 m from an opening in the building directly
opposite, and
b)
so that the products of combustion are not straightly
directed to discharge across a boundary.
1)
Dimensions D, E, F and G:
These clearances may be reduced to 25 mm without
affecting the performance of the boiler. In order to
ensure that the condensate plume does not affect
adjacent surfaces the terminal should be extended as
shown in
¬ fig. 7.6
.
2) Dimension
H:
This clearance may be reduced to 25 mm without
affecting the performance of the boiler. However, in
order to ensure that the condensate plume does not
affect adjacent surfaces a clearance of 300 mm is
preferred. For IE, recommendations are given in the
current edition of IS 813.
For 1 and 2 above you can use the Variable Termination Kit
to move the termination point away from the building fab-
ric.
Article numbers:
0020060584 - White
0020060585 - Black
7.6
Termination of air/flue gas duct under balcony or eaves