8.4

Test menu

As well as the installation assistants, you can also call up the
test menu for start-up, maintenance and troubleshooting.

Menu

Installer level

Test menu

This contains

Statistics

,

Check programmes

and the

Sensor/actuator test

.

8.4.1

Statistics

Menu

Installer level

Test menu

Statistics

This displays the operating hours for:

Solar pump

Solar pump 2

Cylinder pump

8.4.2

Check programmes

Menu

Installer level

Test menu

Check pro-

grammes

The following check programmes are available:

Test solar circuit filling

Start purging programme

8.4.3

Sensor/ actuator test

Menu

Installer level

Test menu

Sensor/actuator

test

The current values of the following sensors can be read off
here:

T1 temperature sensor

T2 temperature sensor

T3 temperature sensor

T4 temperature sensor

T5 collector sensor

T6 cylinder sensor

Cylinder circuit flow rate

Temperature limiter

Solar circuit flow rate

The selection button can be used to activate the following
actuators. You can then use the plus and minus buttons to
change the output/power of the pumps, the flow direction
of the shift-load switching valve or the stratification in the
cylinder.

Solar pump

Solar pump 2

Cylinder pump

UV5 shift-load switching valve

In addition, you can view the approximate

Solar circuit flow

rate

. The value is calculated from the pump output and rota-

tional speed.

8.5

Configuration

You can use the menu

Configuration

to subsequently

change the settings that have been made using the
installation assistant.

Language

Contact details

Date

Time

Summer/winter time

Cascade

Number of collectors

In addition, the following information can be set or read:

Filling time correction

Mode

Heating flow set target temperature

Hot water set target temperature

Shift-load switching valve switch temperature

Maximum cylinder temperature

On temp. diff.

eBUS control

Filling power

Compensation time

Software version

8.5.1

Filling time correction

Menu

Installer level

Configuration

Filling time

corr.

If the filling time is not sufficient for the solar circuit, the filling
time can be extended by up to ten minutes.

8.5.2

Mode

Note

If a system controller is connected, this menu
point does not appear.

Menu

Installer level

Configuration

Operating mode

The operating mode can be set to

Auto

,

High Flow

and

Low Flow

.

Auto

: The solar control attempts to maintain the spread

between the solar supply pipe and the solar return so
that the process water zone in the cylinder is charged at
65 °C. If this is not possible due to low solar radiation, the
heating zone in the cylinder is charged at 40 °C. If this is
not possible either, a spread of 10 K is attempted.

High Flow

: The solar control attempts to maintain the

spread between the solar supply pipe and the solar re-
turn at approx. 10 K. As a rule, this corresponds to 40 l/h
per m

2

collector surface

Low Flow

: The solar control attempts to maintain the

spread between the solar supply pipe and solar return so
that the cylinder is charged at the maximum set cylinder
temperature. As a rule, this corresponds to 15 l/h per m

2

collector surface

Summary of Contents for auroFLOW plus VPM 15 D

Page 1: ... instructions auroFLOW plus VPM 15 D VPM 30 D wiring centre BE de DE Installation and maintenance instructions Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 49 21 91 18 0 Fax 49 21 91 18 2810 info vaillant de www vaillant de ...

Page 2: ...dule 11 6 Installation 12 6 1 Carrying out the hydraulics installation 12 6 2 Carrying out the electrical installation 13 6 3 Completing installation 15 6 4 Installing the expansion module 15 6 5 Installing the second solar pump 16 6 6 Wall mounting the expansion module 18 7 Operation 18 7 1 Operating concept of the solar charger 18 8 Start up 18 8 1 Filling and purging the system 19 8 2 Running t...

Page 3: ...nce with all inspection and main tenance conditions listed in the instruc tions Any other use that is not specified in these instructions or use beyond that specified in this document shall be considered improper use Any direct commercial or industrial use is also deemed to be improper Caution Improper use of any kind is prohibited 1 3 General safety information 1 3 1 Risk caused by inadequate qua...

Page 4: ...oring devices have been removed bridged or disabled Immediately rectify any faults and damage that may affect safety At lengths of over 10 m 230 V supply lines must be laid separately from sensor or bus lines 1 3 7 Risk of material damage caused by using an unsuitable tool Use the correct tool to tighten or loosen screw connections 1 3 8 Damage to the environment as a result of leaking solar fluid...

Page 5: ...uilding as a result of leaking solar fluid Leaking solar fluid may cause damage to the building structure Disconnect the solar charger from the power mains Fix the leaks in the solar system Fill the solar system with solar fluid Switch on the power supply to the solar charger 1 4 Requirements for lines Use standard commercial lines for the wir ing Minimum cross section Supply line 230 V 1 5 mm Sen...

Page 6: ...fety device and expansion vessel If an auroSTOR is in stalled a safety device and expansion vessel are also re quired between the auroSTOR and solar charger Two diverter valves can be installed in the solar system 1 The UV4 which is connected to the auroMATIC VRS 620 3 First priority allSTOR Second priority Swimming pool or other cylinder 2 The UV5 which is connected to the solar charger Switches ...

Page 7: ...p 5 Cylinder charging circuit flow sensor 6 Solar pump 7 Solar system expansion relief valve 8 Solar circuit fill and drain connection 9 Cylinder primary pipework 10 Cylinder return 11 Solar fluid storage tank 12 Retainer for front casing screw 13 Solar controller 14 Solar circuit safety temperature monitor 15 Cylinder charging circuit safety temperature monitor 16 Solar return temperature sensor ...

Page 8: ... instructions auroFLOW plus 0020149486_04 4 2 Design of the auroFLOW plus solar charger basic module and expansion module Note The functional elements of the basic module are described on the previous page 1 2 1 2 Solar fluid storage tank 2 2 Solar pump ...

Page 9: ...n the identification plate The serial number may also be shown on the product s display Operating instructions 4 6 CE label The CE label shows that the products comply with the basic requirements of the applicable directives as stated on the identification plate The declaration of conformity can be viewed at the manufac turer s site 5 Installation 5 1 Storage conditions Store the product in a dry ...

Page 10: ...acilitate maintenance we recommend a clearance of 350 mm 5 8 Clearance from combustible components It is not necessary to maintain a clearance between the product and components made of combustible materials that go beyond the minimum clearances 5 9 Mains connection cable The product is fitted in the factory with a mains connection cable that has to be connected up permanently on site If the mains...

Page 11: ...nstalling the basic module 5 12 1 Removing the front casing A B C D 1 Take hold of the recessed handle at the bottom edge of the white panel 2 Pull the lower edge of the panel forwards and remove the panel by pulling it upwards 3 Undo the bolt 4 Pull the front casing forwards and off 5 12 2 Wall mounting the basic module of the solar charging system Danger Risk of accidents as a result of insuffi ...

Page 12: ...y be carried out by a competent person Note Seals made of rubber like materials may be subject to plastic deformation which can lead to pressure losses We recommend using seals made of a paste like fibre material 6 1 1 Connecting the cylinder charging circuit Note We recommend that the solar charging system be connected to the cylinder charging circuit us ing service valves The service valves are ...

Page 13: ...per son who is responsible for complying with the existing standards and directives Caution Risk of damage to the electrical lines as a result of high temperatures The electrical lines may be damaged by the high temperatures from the solar fluid that flows through the copper pipes Make sure that the electrical lines are not positioned directly next to the pipes through which the solar fluid flows ...

Page 14: ...rrent sensitive RCDs type A or universal RCDs type B with short time delay VSK Connect the product using a fixed connection and a partition with a contact opening of at least 3 mm e g fuses or power switches see Mains connection cable Page 10 6 2 3 Connecting the collector temperature sensor cylinder temperature sensor and system controller Note Only carry out points 6 and 7 if an external system ...

Page 15: ...p must be installed To connect the two storage tanks the controller bracket and the storage tank of the basic module must first be removed When you need to work on the basic module and the expansion module this work can be made easier if the modules are on the floor Carry out the work steps in this section one after the other and in the exact sequence that is described here 6 4 1 Removing the cont...

Page 16: ...e connec tion pipes through the openings in the side panel of the casing 6 4 4 Fitting the controller bracket 1 Slide the controller bracket 1 over the pipes until it clicks into place 6 5 Installing the second solar pump 6 5 1 Connecting the hydraulic lines of the second solar pump 2 3 4 1 1 Find the control cable of the second solar pump in the cable harness 3 2 Route the control cable through t...

Page 17: ...emperatures The electrical lines may be damaged by the high temperatures from the solar fluid that flows through the copper pipes Make sure that the electrical lines are not positioned directly next to the pipes through which the solar fluid flows 2 1 1 1 Undo the four bolts 1 2 Open the controller casing 3 Remove the dummy plugs 2 X1 X3 X2 X8 X7 X6 X5 X4 eBUS N L1 L2 4 5 3 4 Route the power cable...

Page 18: ...operator level are also described in the operating instructions An overview of the menu structure at the installer level is included in the appendix Page 29 7 1 1 Calling up the installer level Caution Risk of damage caused by incorrect hand ling Incorrect settings at installer level may cause damage to the solar plant You must only access the installer level if you are an approved competent perso...

Page 19: ...ging circuit using the pressure gauge that is available on site and add extra water as required 6 Check the cylinder charging circuit for leak tightness Conditions The cylinder is an auroSTOR Fill the cylinder charging circuit with suitable heating water Flush out the cylinder thoroughly so that the air can es cape from the pipe coil Check the pressure in the cylinder charging circuit While doing ...

Page 20: ... is star ted the installation assistant starts again Switch on the power supply to the product 8 2 1 Setting the language Note If a system controller has been connected the language can only be set on the system controller 1 Set the desired language using or 2 Press to confirm the set language 3 Press again to confirm the language a second time and to prevent it being changed unintentionally 8 2 2...

Page 21: ...on time Page 24 Danger Risk of personal injury due to incorrect pressure compensation Solar fluid or hot vapour escaping from the purging valve may cause serious scalding The following instruction must be followed when carrying out the pressure compens ation If you open the purging valve while the solar pump is running you must do so carefully Some solar fluid may be emitted under pressure from th...

Page 22: ...pressure compensation Solar fluid or hot vapour escaping from the purging valve may cause serious scalding The following instruction must be followed when carrying out the pressure compens ation 1 2 Carry out the pressure compensation immediately after completing the installation assistant and if required re peat the procedure once again on that same evening if the solar plant has cooled down Conn...

Page 23: ...Configuration to subsequently change the settings that have been made using the installation assistant Language Contact details Date Time Summer winter time Cascade Number of collectors In addition the following information can be set or read Filling time correction Mode Heating flow set target temperature Hot water set target temperature Shift load switching valve switch temperature Maximum cylin...

Page 24: ...ps may suck in air To prevent this the two solar pumps are started up separately During the first stage only the lower solar pump is running You can use the Compensa tion time setting to adjust the length of the first stage Set the compensation time so that the solar fluid level is approx imately 5 cm in both storage tanks before the second solar pump is activated 8 5 10 Software version Menu Inst...

Page 25: ...llector fastenings and connections Annually Inspection and maintenance work Interval Check that the brackets and collector com ponents are clean and fitted properly Annually Check the pipe insulations for damage Annually Solar controller Check the pump function Annually Check the sensor temperature display Annually Check the solar yield for plausibility Annually Check the filling loop Annually Cyl...

Page 26: ...ometer 11 5 2 Draining the solar fluid Preliminary work Switch off the solar system by interrupting the power supply 3 1 2 1 Connect a hose that runs down to the floor from the purging valve 1 2 Place the end of the hose in a collecting container that is suitable for storing solar fluid 2 and which has suf ficient capacity 20 l or 40 l capacity Hold the hose in the collecting container in such a w...

Page 27: ...devices Close all available isolator devices in the cylinder char ging circuit on site 12 2 Permanently decommissioning the product 12 2 1 Switching off the solar charging system Disconnect the product by de energising it using a parti tion with a contact opening of at least 3 mm e g fuses or power switches 12 2 2 Completely draining the solar and heating installation 1 Completely drain the heatin...

Page 28: ... auroFLOW plus 0020149486_04 B 1620 Drogenbos Belgien Belgique België Kundendienst Service après vente Klantendienst 2 3349352 Applicability Germany Vaillant Profi Hotline 018 06 999120 20 Cent Anruf aus dem deutschen Festnetz aus dem Mobilfunknetz max 60 Cent Anruf ...

Page 29: ... P 07 Back Test solar circuit filling Select T 40 Back T1 temperature sensor 14 1 C Test menu Back Select Statistics Check programmes Sensor actuator test P 07 Cancel Test solar circuit filling Test active Statistics Cylinder charge pump Back Select Solar pump Solar pump 2 Solar pump 2 Back Operating hours 20 Statistics Cylinder charge pump Back Select Solar pump Solar pump 2 Cylinder charge pump ...

Page 30: ...of collectors Filling time corr Back 0 Filling time corr Configuration Back Select Filling time corr Operating mode Heating temperature Back Target temperature of heating flow 0 Configuration Back Select Number of collectors Filling time corr Operating mode Back Automatic Configuration Back Select Operating mode Heating temperature DHW temp Back Target temperature of domestic hot water 0 DHW temp ...

Page 31: ...istant press OK OK Configuration Back Select Max cylinder temp Switch on diff eBUS controller Back Not detected eBUS controller Configuration Back Select Switch on diff eBUS controller Filling power Back 0 Filling power Configuration Back Select eBUS controller Filling power Compensation time Back 0 Compensation time Configuration Back Select Filling power Compensation time Software version Back S...

Page 32: ...min Check the solar circuit for siphons Cylinder charging pump is running how ever the solar pump is not running Overrun function solar charging stopped shortly before No fault Cylinder charging pump running at low outside temperatures Frost protection function No fault Collector temperature very high and solar system starts filling Hot starts are possible as a result of Drain back technology No f...

Page 33: ...wing of the storage tank is normal very strong rapid discolouration is an in dication of high temperatures in the solar circuit Check the solar circuit function Check the cylinder charging circuit function The solar fluid level falls over time Solar circuit leaking Find and seal any leaks Pressure too high and expansion relief valve discharges Check the expansion relief valve function Check that t...

Page 34: ...on and maintenance instructions auroFLOW plus 0020149486_04 VPM 15 D basic module VPM 30 D ba sic module with expansion module Product dimensions depth 340 mm 340 mm Collector surface area 15 m 30 m Number of collectors 6 12 ...

Page 35: ... charging system 27 Disposing of the solar fluid 27 Documents 6 Draining the solar fluid 26 E Electricity 3 F Filling the cylinder charging circuit 19 Filling the storage tank 19 Frost 4 H Handing over the solar charging system 24 Hand over operator 24 I Installation assistant 20 Installer level 18 Installing the front casing 15 Instructions validity 6 Intended use 3 L Leaking heating installation...

Page 36: ...Telefax 021 91 18 2810 Vaillant Profi Hotline 018 06 999120 20 Cent Anruf aus dem deutschen Festnetz aus dem Mobilfunknetz max 60 Cent Anruf Vaillant Kundendienst 018 06 999150 20 Cent Anruf aus dem deutschen Festnetz aus dem Mobilfunknetz max 60 Cent Anruf info vaillant de www vaillant de These instructions or parts thereof are protected by copyright and may be reproduced or distributed only with...

Reviews: