Appendix
28
Installation and maintenance instructions aroCOLLECT 0020217119_01
VWF 57/4
VWF 87/4
VWF 117/4
VWF 157/4
VWF 197/4
Power consumption A7/W55
Δ
T 8 K
2.00 kW
3.00 kW
3.90 kW
5.00 kW
6.70 kW
Output figure A7/W55
Δ
T 8 K/coefficient
of performance EN 14511
3.10
3.20
3.20
3.30
3.20
Cooling output A35/W18
Δ
T 5 K, active
6.60 kW
8.60 kW
12.10 kW
15.80 kW
22.30 kW
Power consumption A35/W18
Δ
T 5 K, act-
ive
1.60 kW
2.80 kW
3.70 kW
4.40 kW
6.20 kW
Energy efficiency ratio A35/W18 EN 14511
4,30
3,20
3,40
3,90
3,40
Sound power level A7/W35
EN 12102/EN 14511 L
WI
in heating mode
40.3 dB(A)
45.8 dB(A)
44.4 dB(A)
48.7 dB(A)
48.1 dB(A)
Sound power level A7/W45
EN 12102/EN 14511 L
WI
in heating mode
41.0 dB(A)
50.1 dB(A)
46.4 dB(A)
49.4 dB(A)
46.1 dB(A)
Sound power level A7/W55
EN 12102/EN 14511 L
WI
in heating mode
40.9 dB(A)
52.7 dB(A)
46.1 dB(A)
48.0 dB(A)
46.4 dB(A)
Sound power level A35/W18
EN 12102/EN 14511 L
WI
in cooling mode
48.3 dB(A)
54.7 dB(A)
49.7 dB(A)
46.8 dB(A)
47.2 dB(A)
Application limits for the heat pump: Heating and cooling (heat source = air)
At the same volume flow rates in the heating circuit (
Δ
T 5K or
Δ
T 8 K) as for the nominal heat output test under standard
nominal conditions.
Operation of the pump outside the application limits results in the heat pump being switched off by the internal control and
safety devices.
VWF 58/4
VWF 88/4
VWF 118/4
Application limits for the heat pump: Heat-
ing (Air heat source)
–
A40/W65
–
A40/W25
–
A
−
22/W25
–
A
−
22/W50
–
A
−
2/W65
–
A15/W65
–
A40/W65
–
A40/W25
–
A
−
22/W25
–
A
−
22/W50
–
A
−
2/W65
–
A15/W65
–
A40/W65
–
A40/W25
–
A
−
22/W25
–
A
−
22/W50
–
A
−
2/W65
–
A15/W65
Application limits for the heat pump: Cool-
ing (Air heat source)
–
A20/W20
–
A40/W20
–
A40/W5
–
A20/W5
–
A20/W20
–
A40/W20
–
A40/W5
–
A20/W5
–
A20/W20
–
A40/W20
–
A40/W5
–
A20/W5
Application limits for the heat pump: Heating (heat source = air)
At the same volume flow rates in the heating circuit (
Δ
T 5K or
Δ
T 8 K) as for the nominal heat output test under standard
nominal conditions.
Operation of the pump outside the application limits results in the heat pump being switched off by the internal control and
safety devices.
VWF 57/4
VWF 87/4
VWF 117/4
VWF 157/4
VWF 197/4
–
A40/W65
–
A40/W25
–
A
−
22/W25
–
A
−
22/W50
–
A
−
2/W65
–
A15/W65
–
A40/W65
–
A40/W25
–
A
−
22/W25
–
A
−
22/W50
–
A
−
2/W65
–
A15/W65
–
A40/W65
–
A40/W25
–
A
−
22/W25
–
A
−
22/W50
–
A
−
2/W65
–
A15/W65
–
A40/W65
–
A40/W25
–
A
−
22/W25
–
A
−
22/W50
–
A
−
2/W65
–
A15/W65
–
A40/W65
–
A40/W25
–
A
−
22/W25
–
A
−
22/W50
–
A
−
2/W65
–
A15/W65
Application limits for the heat pump: Cooling (heat source = air)
At the same volume flow rates in the heating circuit (
Δ
T 5K or
Δ
T 8 K) as for the nominal heat output test under standard
nominal conditions.
Operation of the pump outside the application limits results in the heat pump being switched off by the internal control and
safety devices.
VWF 57/4
VWF 87/4
VWF 117/4
VWF 157/4
VWF 197/4
–
A20/W20
–
A40/W20
–
A40/W5
–
A20/W5
–
A20/W20
–
A40/W20
–
A40/W5
–
A20/W5
–
A20/W20
–
A40/W20
–
A40/W5
–
A20/W5
–
A20/W20
–
A40/W20
–
A40/W5
–
A20/W5
–
A20/W20
–
A40/W20
–
A40/W5
–
A20/W5