TECHNICAL DATA
vacon • 21
4
4.2.3
Vacon NX_2 – Mains voltage 208—240 V
High overload = Max current IS, 2 sec/20 sec, 150% overloadability, 1 min/10 min
Following continuous operation at rated output current, 150 % rated output current (IH)
for 1 min, followed by a period of load current less than rated current, and of such
duration that the r.m.s output current, over the duty cycle, does not exceed rated
output current (IH)
Low overload = Max current IS, 2 sec/20 sec, 110% overloadability, 1 min/10 min
Following continuous operation at rated output current, 110% rated output current (IL)
for 1 min, followed by a period of load current less than rated current, and of such
duration that the r.m.s output current, over the duty cycle, does not exceed rated
output current (IL)
All sizes are available as IP21/NEMA1 or IP54/NEMA12.
Mains voltage 208-240 V, 50/60 Hz, 3~
AC drive
type
Loadability
Motor shaft power
Frame
Dimensions and
weight
WxHxD/kg
(in/lb)
Low
High
230V supply
208-240V
supply
Rated
continuous
current I
L
(A)
10%
overload
current
(A)
Rated
continuous
current I
H
(A)
50%
overload
current
(A)
Max
current
I
S
10%
overload
104 °F
P(HP)
50%
overload
122 °F
P(HP)
10%
overload
104 °F
P(hp)
50%
overload
122 °F
P(hp)
NX_ 0004 2
4.8
5.3
3.7
5.6
7.4
1
0.7
1
0.75
FR4
5.0x11.5x7.5/11
NX_ 0007 2
6.6
7.3
4.8
7.2
9.6
1.5
1
1.5
1
FR4
5.0x11.5x7.5/11
NX_ 0008 2
7.8
8.6
6.6
9.9
13.2
2
1.5
2
1.5
FR4
5.0x11.5x7.5/11
NX_ 0011 2
11
12.1
7.8
11.7
15.6
3
2
3
2
FR4
5.0x11.5x7.5/11
NX_ 0012 2
12.5
13.8
11
16.5
22
4
3
-
3
FR4
5.0x11.5x7.5/11
NX_ 0017 2
17.5
19.3
12.5
18.8
25
5.4
4
5
-
FR5
5.7x15.4x8.4/17.9
NX_ 0025 2
25
27.5
17.5
26.3
35
7.4
5.4
7.5
5
FR5
5.7x15.4x8.4/17.9
NX_ 0031 2
31
34.1
25
37.5
50
10
7.4
10
7.5
FR5
5.7x15.4x8.4/17.9
NX_ 0048 2
48
52.8
31
46.5
62
14.7
10
15
10
FR6
7.7x20.4x9.3/40.8
NX_ 0061 2
61
67.1
48
72.0
96
20
14.7
20
15
FR6
7.7x20.4x9.3/40.8
NX_ 0075 2
75
83
61
92
122
29.4
20
25
20
FR7
9.3x23.3x10.1/77.2
NX_ 0088 2
88
97
75
113
150
29.4
29.4
30
25
FR7
9.3x23.3x10.1/77.2
NX_ 0114 2
114
125
88
132
176
40
29.4
40
30
FR7
9.3x23.3x10.1/77.2
NX_ 0140 2
140
154
105
158
210
50
40
50
40
FR8
11.5x29.8x13.5/127.9
NX_ 0170 2
170
187
140
210
280
60
50
60
50
FR8
11.5x29.8x13.5/127.9
NX_ 0205 2
205
226
170
255
336
74
60
75
60
FR8
11.5x29.8x13.5/127.9
NX_ 0261 2
261
287
205
308
349
101
74
100
75
FR9
18.9x45.3x14.3/321.9
NX_ 0300 2
300
330
245
368
444
121
101
125
100
FR9
18.9x45.3x14.3/321.9
Table 4-3. Power ratings and dimensions of Vacon NX, supply voltage 208—240V.
Note: The rated currents in given ambient temperatures are achieved only when the switching frequency is
equal to or less than the factory default.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]