cabling and connections
vacon 51
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6
6.1.2
Installation instructions
1
Before starting the installation, check that none of the components of the
inverter are live.
2
In accordance with protection class IP00 requirements. There is no need
to install the inverter cover if the inverter is installed in a cubicle,
separate cabinet or device space.
3
Place the motor cables sufficiently far from other cables:
▪
Avoid placing the motor cables in long parallel lines with other
cables
▪
If the motor cables runs in parallel with other cables, note the
minimum distances between the motor cables and other cables
given in the table below.
▪
The given distances also apply between the motor cables and
signal cables of other systems.
▪
The maximum length of the motor cables is 300 m.
If output du/dt filters (+DUT option) are used the cable length is
limited according to the table below:
▪
The motor cables should cross other cables at an angle of 90
degrees.
4
If cable insulation checks are needed, see Chapter .
Distance
between cables
[m]
Shielded
cable
[m]
0.3
50
1.0
200