18 vacon
technical data
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
4
4.2.2
Supply voltage 640-1100 Vdc, Motor voltage 525
690 Vac
All enclosures are available as IP21 and IP54.
Motor voltage 525-690 Vac, 50/60 Hz, 3~
Inverter type
Loadability
@ 40 °C ambient temperature
Motor shaft
power
Enclos
ure
size
Dimensions and weight
W
×
H
×
D/kg
Low
High
930Vdc
supply
Rated
continuou
s current
I
L
(A)
10%
overload
current
(A)
Rated
continuous
current
I
H
(A)
50%
overload
current
(A)
Max
current
I
S
10%
overload
40°C P(kW)
50%
overload
40°C
P(kW)
NXI_0125 6
125
138
100
150
200
110
90
FI9
239 × 1030 × 372/65
NXI_0144 6
144
158
125
188
213
132
110
FI9
239 × 1030 × 372/65
NXI_0170 6
170
187
144
216
245
160
132
FI9
239 × 1030 × 372/65
NXI_0208 6
208
229
170
255
289
200
160
FI9
239 × 1030 × 372/65
NXI_0261 6
261
287
208
312
375
250
200
FI10
239 × 1030 × 552/100
NXI_0325 6
325
358
261
392
470
315
250
FI10
239 × 1030 × 552/100
NXI_0385 6
385
424
325
488
585
355
315
FI10
239 × 1030 × 552/100
NXI_0416 6
416
458
325
488
585
400
355
FI10
239 × 1030 × 552/100
NXI_0460 6
460
506
385
578
693
450
400
FI12
2×239 × 1030 × 552/200
NXI_0502 6
502
552
460
690
828
500
450
FI12
2×239 × 1030 × 552/200
NXI_0590 6
590
649
502
753
904
560
500
FI12
2×239 × 1030 × 552/200
NXI_0650 6
650
715
590
885
1062
630
560
FI12
2×239 × 1030 × 552/200
NXI_0750 6
750
825
650
975
1170
710
630
FI12
2×239 × 1030 × 552/200
NXI_0820 6
820
902
650
975
1170
800
710
FI12
2×239 × 1030 × 552/200
NXI_0920 6
920
1012
820
1230
1476
900
800
FI13
708 × 1030 × 553/302
NXI_1030 6
1030
1133
920
1380
1656
1000
900
FI13
708 × 1030 × 553/302
NXI_1180 6
1180
1298
1030
1464
1755
1200
1000
FI13
708 × 1030 × 553/302
NXI_1500 6
1500
1650
1300
1950
2340
1500
1300
FI14
2×708 × 1030 × 553/302
NXI_1900 6
1900
2090
1500
2250
2700
1800
1500
FI14
2×708 × 1030 × 553/302
NXI_2250 6
2250
2475
1900
2782
3335
2000
1800
FI14
2×708 × 1030 × 553/302
Table 4
-
2. Power ratings and dimensions of VACON
®
NXI, supply voltage 640 1100Vdc
Note: The rated currents in given ambient temperatures are achieved only when the switching
frequency is equal to or less than the factory default.
4.2.3
Overload capability
The low overload means that if 110% of the continuous current (IL) is required for 1 minute
every 10 minutes, the remaining 9 minutes must be approximately 98% of IL or less. This is to
make sure that the output current is not more than IL during the duty cycle.