7
vacon • 30
Maintenance
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
30
Safety configuration
507
The hardware does not support
the OPTBJ board.
• Restart the drive.
• Should the fault re-occur, con-
tact the distributor near to you.
30
Safety diagnostics
520
There is a diagnostic failure in
the STO safety function. This
fault occurs when the STO
inputs are in a different state for
more than 100 ms.
• Restart the drive.
• If the restart does not help,
change the OPTBJ board.
• Should the fault re-occur, con-
tact the distributor near to you.
Deliver the fault report to the
distributor, see fault details for
more information.
30
Safety diagnostics
521
Atex-thermistor diagnostic
fault.
• Restart the drive.
• If the restart does not help,
change the OPTBJ board.
• Should the fault re-occur, con-
tact the distributor near to you
30
Safety diagnostics
522
Atex-thermistor short-circuit.
• Check the connection of the
Atex-thermistor
• Check the thermistor
• Restart the drive.
• If the restart does not help,
change the OPTBJ board.
• Should the fault re-occur, con-
tact the distributor near to you
30
Safety diagnostics
523
Problem occured in internal
safety circuit
• Reset the drive and restart. If
the fault reoccurs contact your
nearest distributor.
30
Safety diagnostics
524
Overvoltage detected in safety
option board
• Reset the drive and restart. If
the fault reoccurs contact your
nearest distributor.
30
Safety diagnostics
525
Undervoltage detected in safety
option board
• Reset the drive and restart. If
the fault reoccurs contact your
nearest distributor.
30
Safety diagnostics
526
Internal failure detected in
safety option board CPU or
memory handling
• Reset the drive and restart. If
the fault reoccurs contact your
nearest distributor.
30
Safety diagnostics
527
Internal failure detected in
safety function
• Reset the drive and restart. If
the fault reoccurs contact your
nearest distributor.
Fault code
Fault
ID
Explanation
Correcting measures
Summary of Contents for 100 INDUSTRIAL
Page 1: ...vacon 100 ac drives optbj sto and atex option board safety manual...
Page 2: ......
Page 4: ...1 vacon 2 Approvals Tel 358 0 201 2121 Fax 358 0 201 212 205 1 APPROVALS...
Page 5: ...Approvals vacon 3 24 hour support 358 0 201 212 575 Email vacon vacon com 1...
Page 6: ...1 vacon 4 Approvals Tel 358 0 201 2121 Fax 358 0 201 212 205...
Page 7: ...Approvals vacon 5 24 hour support 358 0 201 212 575 Email vacon vacon com 1...
Page 8: ...1 vacon 6 Approvals Tel 358 0 201 2121 Fax 358 0 201 212 205...
Page 9: ...Approvals vacon 7 24 hour support 358 0 201 212 575 Email vacon vacon com 1...