Thermistor function (ATEX)
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8.1.4
Short circuit monitoring
The thermistor inputs TI1+ and TI1- are monitored for short circuit. If a short circuit is detected, the
drive modulation is disabled within 20ms, Fault 30, Safety diagnostic (subcode 522) is generated.
When the short circuit has been removed, the drive can be reset only after a power recycle.
The short circuit monitoring can be enabled or disabled using the jumper X23 in ON or OFF position
respectively. The jumper is set in ON position by factory default.