STO and SS1 safety functions
vacon • 19
24-hour s358 (0)201 212 575 • Email: [email protected]
5
Figure 8 shows the connection principle of Safe Stop 1 safety function, as specified in figure 6.
•
The time delayed safety relay outputs are connected to the STO inputs.
•
A separate digital output from the safety relay is connected to a general digital input of the
Vacon 100 drive. The general digital input must be programmed to execute the drive stop
command and initiates the drive stop function without a time delay (must be set to "stop by
ramp") and causes motor deceleration. If the SS1 behavior of Figure 6 is required then it
must be ensured that the ramp stop is activated when the stop signal is received. It is the
responsibility of the system designer to verify this.
Figure 8. The connection principle of Safe Stop 1 (SS1)
See Chapter 5.4 concerning the parametrizing of Safe Stop 1 and Chapter 5.3.5 for the wiring of Safe
Stop 1.
CAUTION!
The system designer/user is responsible for understanding and setting
the time delay of the safety relay, as it is process/machine dependent.
•
The time delay must be set to a greater value than the deceleration time of
the drive*. The motor deceleration time is process/machine dependent.
•
The stop function of the drive needs to be correctly set for the process/
machine. Activating the SS1 safety function must execute the configured
stop in the drive. In the Vacon 100 default application software it is recom-
mended to use the "Quick Stop" functionality for this purpose.
* In case of a single fault the drive may not ramp down but is only put to STO mode after the config-
ured time delay.
CAUTION!
The control place must be set according to the application require-
ments.
M
Switch
Safety Relay
with timer
Vacon 100
control
Basic I/O
Digital input
OPTBJ board
STO channel 1
STO channel 2
Time
delay
Power Unit
Ramp stop
STO
11577_uk
13006.emf
13006.emf
Summary of Contents for 100 INDUSTRIAL
Page 1: ...vacon 100 ac drives optbj sto and atex option board safety manual...
Page 2: ......
Page 4: ...1 vacon 2 Approvals Tel 358 0 201 2121 Fax 358 0 201 212 205 1 APPROVALS...
Page 5: ...Approvals vacon 3 24 hour support 358 0 201 212 575 Email vacon vacon com 1...
Page 6: ...1 vacon 4 Approvals Tel 358 0 201 2121 Fax 358 0 201 212 205...
Page 7: ...Approvals vacon 5 24 hour support 358 0 201 212 575 Email vacon vacon com 1...
Page 8: ...1 vacon 6 Approvals Tel 358 0 201 2121 Fax 358 0 201 212 205...
Page 9: ...Approvals vacon 7 24 hour support 358 0 201 212 575 Email vacon vacon com 1...