5
vacon • 18
STO and SS1 safety functions
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
5.2
Safe Stop 1 (SS1) Principle
After a safe stop command the motor starts decelerating and SS1 safety function initiates the STO
after a user set time delay.
Figure 6. The principle of Safe Stop 1 (EN 61800-5-2, SS1 type c)
The Safe Stop 1 (SS1) safety function consists of two safety related subsystems, an external time
delayed safety relay and the STO safety function. These two subsystems combined compose the
Safe Stop 1 safety function as shown in Figure 7.
Figure 7. Safe Stop 1 (SS1) safety function
Time
0
Stop
Motor
deceleration
Frequency
f
actual
Time delay
Safe Torque Off (STO)
11578_uk
Safe Stop 1 (SS1)
Time Delayed Safety Relay
Vacon 100 Safe Torque Off (STO)
+
Subsystem
Safety Relay
Subsystem
STO
11579_uk