PHOTO 1 INPUT 

This input can be activated for the connection of two diffe-
rent safety devices: the photocell or the rib. The rib (contact
normally closed) is an active safety device in opening and
closing (now active during the backlash): its inter vention
during the opening phase stops the gate, inverts the motion
for 4 s, without offsetting the doors. On the other hand, the
inter vention of the rib in closing phase stops the gate,
inver ts the motion with the offset of the doors. The photocell
1 (contact normally closed) is an active security in opening
and closing: the inter vention of the photocell during the clo-
sing stops the gate, at its disengagement the gate inver ts
the motion. 
Differently the inter vention of the photocell in opening stops
the gate, at its disengagement the gate star ts opening again.
It is necessar y to install the photocell 1 properly, in order to
cover the action space of the gate.

no

the opening of PHOTO1 is not available

Cost

the opening of PHOTO 1 is available for the connection
of the rib.

APCh

the opening of PHOTO 1 is available for the connection
of the photocell

TIMER FUNCTION

This function permits to program the time bands of opening
and closing. It is necessar y to connect a 24h timer with a
contact normally open in parallel with the START or PEDE-
STRIAN START input. When the timer contact is closed, the
gate gets into opening phase and remains opened until the
contact of the timer opens causing the re-closing of the gate.

IMPORTANT

: for a correct functioning it is necessar y to 

activate the automatic closing (menu Ch.AU.)

FLASHLIGHT WITH INTERMITTENCE

The control unit PD9 permits the connection of a flashlight
with or without intermittence. If the flashlight is equipped with
an inner intermittence effect, it is necessar y to select the
option "Si", but if it has no inner intermittence, it is neces-
sar y to select the option "no" in order to make it flash. 

STOP INPUT 

This menu permits to select the functions associated to the 
command of STOP.

no

the input STOP is not available

ProS

the input STOP stops the gate: pressing the command 
START the gate continues the motion

invE

the command STOP stops the gate: at the next START
the gate star ts moving in the opposite direction.

NOTE: during the pause, the STOP command will stop the
pause time count, the next START command will always close
the gate. 

Summary of Contents for PD9

Page 1: ...ND DOUBLE SWING GATES I GB GATESTORE Ltd 682 Anlaby High Rd Kingston Upon Hull HU3 6UZ tel 0845 226 3123 fax 01482 505001 info gatestore co uk www vidue co uk COMPANY WITH QUALITY SYSTEM CERTIFIED BY QMSI UNI EN ISO9001 IL n 155 EDIZ 05 05 03 ...

Page 2: ...TRIAN GATE 20 CLOSING TIME GATE 1 20 CLOSING TIME GATE 2 20 CLOSING OF PEDESTRIAN GATE 20 GATE DELAY DURING OPENING 20 GATE DELAY DURING CLOSING 21 LOCK TIME 21 BACKLASH TIME 21 PRE FLASHING TIME 21 MOTOR POWER 1 21 MOTOR POWER 2 21 START SLOWING DOWN 21 END OF STROKE SLOWING DOWN 21 START IN OPENING 22 START IN CLOSING 22 START IN PAUSE 22 PEDESTRIAN START IN OPENING 22 THE PHOTOCELL IN PAUSE 22 ...

Page 3: ...evel Installation requires mechanical and electrical skills therefore it shall be carried out by qualified personnel only who can issue the Compliance Certificate concerning the whole installation EEC Machine Directive 89 392 Annex IIA The automated vehicular gates shall comply with the following rules EN 12453 EN 12445 EN 12978 as well as any local rule in force Also the automation upstream elect...

Page 4: ...4 channels and each of them is suitable for a command of PD9 control unit CHANNEL 1 START CHANNEL 2 PEDESTRIAN START CHANNEL 3 STOP CHANNEL 4 COURTESY LIGHTS Before programming 4 channels and function logics read carefully the instructions of MR1 WARNING we suggest to use the external aerial model ANS433 in order to guarantee the maximal range TERMINAL CONNECTION Antenna Antenna shield Opening con...

Page 5: ...ng these time menus have been placed in the function menus on which they depend Specifically menus AUTOMATIC CLOSING Ch AU and PHOTOCELL TIME OUT Ft PA offer some time menus among the selectable options FUNCTION OF KEYS MENU UP DOWN To activate the program mode proceed as follows After powering the unit the display should show the control panel therefore check that the connections made are correct...

Page 6: ...ckout function is required a no maintenan ce lead accumulator needs to be connected by means of special coupling terminals by strictly complying with the silk screen printing polarities of the control card The accumulator shall have the following characteristics TYPE lead and with no maintenance need VOLTAGE 12 VOLT CAPACITY 4 2 Ah Position the battery according to the figure and use the areas ind...

Page 7: ... menu is adjustable from 0 to 2 minutes and determines the time of opening of gate 2 WARNING if it is a one door gate such time shall be set up on 0 OPENING TIME OF PEDESTRIAN GATE This menu is adjustable from 0 seconds to t AP1 and determines the opening time of pedestrian gate CLOSING TIME GATE 1 This menu is adjustable from 0 to 2 minutes which is the closing time for gate 1 To avoid the uncomp...

Page 8: ... or in closing phase the time of pre flashing can be adjusted from 0 to 2 minutes END OF STROKE SLOWING DOWN Such a menu allows enabling the door slowing down at their end of stroke by means of two speeds which can be set up according to your needs vEL1 corresponds to 25 of power vEL2 corresponds to 50 of power MOTOR 1 POWER Such a menu enables the sensitivity adjusting of the motor 1 current sens...

Page 9: ...g has been activated menu Ch AU PEDESTRIAN START IN OPENING This menu permits to select the functions of the command of START P during the opening phase PAUS the command PEDESTRIAN START stops the gate and goes in pause ChiU the command PEDESTRIAN START closes the gate no the command PEDESTRIAN START is not available THE PHOTOCELL IN PAUSE This menu permits to determine the functioning of two phot...

Page 10: ... is also possible to control this connection using the code memorized in the radio input tEL4 in this last case the con nection courtesy light becomes an auxiliary connection to which it is possible to match one of the following functional logics monostable it activates the output relay through all the tx transmission time when the transmission ends the relay is disconnected bistable it activates ...

Page 11: ...he connection of the photocell TIMER FUNCTION This function permits to program the time bands of opening and closing It is necessary to connect a 24h timer with a contact normally open in parallel with the START or PEDE STRIAN START input When the timer contact is closed the gate gets into opening phase and remains opened until the contact of the timer opens causing the re closing of the gate IMPO...

Page 12: ...ATA HAVE BEEN MEMORIZED THE CONTROL UNIT IS READY TO BE USED COUNTER VIEWING Such a menu allows viewing the number of opera tion cycles which such automatism carries out and it also enables the final user to set up a limit value in order to show him when the actuators service is required tot Total number of completed cycles the display views in thousands press DOWN to view units SErv number of cyc...

Page 13: ...lock operation time Lock is not energized it corresponds to 0 Backlash time Disabled recoil it corresponds to 0 Pre flashing time Disabled pre blink it corresponds to 0 Under stress motor 1 alarm threshold it deals with a conventional number Under stress motor 2 alarm threshold it deals with a conventional number Start slowing down End of stroke slowing down Motor slowing down at speed 1 Disabled ...

Page 14: ...OP input not available STOP command stops the gate pressing the START command gate continues the motion STOP command stops the gate START command starts moving in the opposite direction PHOTO 1 input Not available Input is available for the connection of the rib Input is available for the connection of the photocell PHOTO 2 input Photocell is active in closing and also when the gate is still Not a...

Page 15: ...28 NOTE ...

Reviews: