background image

E

N

G

L

IS

H

35

4.3 - STOP

For a better safety, you can fit a stop switch that will cause the
immediate gate stop when activated. This switch must have a
normally close contact (NC) that will get open in case of
operation.
In case the STOP switch is operated while the gate is open, the
automatic closing function will always be disabled. To close the
gate again, you will need a start command (if the start function
in pause is disabled, it will be temporarily enabled to allow the
gate release).

Connect the stop switch cables between terminal 

J3 (STOP)

and

J4 (COM) 

of the control unit.

The stop switch function can be activated by means of a
remote control stored on channel 3 (see relevant instructions of
MRx receiver).

m

PHOTOCELLS - INSTRUCTIONS

• The control unit powers the photocells at a nominal voltage of 

24 Vdc, with an electronic fuse that breaks the current in the 
case of an overload.

• If the transmitter power supply is connected to terminals 

E3 (+)

and 

E2 (-)

, the control unit can perform the photocell 

operation test prior to starting gate opening. 

• The photocells on the interior side should be installed so as to 

completely cover the gate opening area. 

• If several pairs of photocells are installed on the same side of 

the gate, the receiver N.C. outputs should be connected in 
series.

• The photocells are not powered when the control unit is in 

ENERGY SAVING mode.

4.4 - CONNECTING PHOTOCELLS

The control unit considers two kinds of photocells, depending on
the terminal to which they are connected:

Photocell 1:

that is to say, photocells installed on the gate 

inner side, which are active both during the opening and the 
closing phase. When photocells 1 operate, the control unit 
stops the gate; as soon as the photocell beam is free, the 
control unit will open the gate completely.

Photocell 2:

that is to say, photocells installed on the 

external gate side and which are active during the closing
phase only. When photocells 2 operate, the control unit 
opens the gate immediately, without waiting for release.

• Connect power supply cables of photocells transmitter 

between terminals 

E3 (+)

and 

E2 (-)

of the control unit.

• Connect power supply cables of photocells receiver 

between terminals 

E1 (+)

and 

E2 (-)

of the control unit.

• Connect receiver output of photocells 1 between terminals 

J5 (PHOTO1)

and 

J9 (COM)

of the control unit and receiver 

output of photocells 2 between terminals 

J6 (PHOTO2)

and 

J9 (COM)

of the control unit. 

Use outputs having normally closed contact. 

m

SAFETY RIBBONS - INSTRUCTIONS

• If several edges, with normally closed contacts, are used, the 

outputs should be connected in series.

• If several conductive rubber edges are used, the outputs should 

be connected in cascade, and only the final edge should be 
terminated on the nominal resistance.

• Active edges connected to the accessory power supply are 

inactive when the control unit switches to ENERGY SAVING 
mode.

• To meet the requirements of EN12978, it is necessary to install 

conductive rubber sensitive edges; contact normally closed 
sensitive edges should have a control unit that constantly 
verifies their correct operation. If control units with the option 
to conduct testing by interrupting the power are used, connect 
the control unit power cables between terminals 

E3 (+) 

and 

E2 (-)

on the PD13.

Otherwise, connect them between terminals 

E1 (+) 

and 

E2 (-)

.

Testing the edges should be activated by means of the

Co.tE

menu.

4.5 - CONNECTING SAFETY RIBBONS

The control unit considers two kinds of safety ribbons,
depending on the terminal to which they are connected:

Type 1 (fixed): 

they are mounted on walls or on other fixed

obstacles that are approached by the gate doors during the
opening phase. When type 1 safety ribbons operate during
the gate opening phase, the control unit will close the doors
for 3 seconds, then it stands still; when type 1 safety ribbons 
operate during the gate closing phase, the control unit will 
stand still immediately. The direction of the gate at next 
command of START or PEDESTRIAN START depends upon the 
parameter STOP (it inverts or continues the motion). 
If the input STOP is disabled, the command makes the motion 
continue in the same direction.

Type 2 (mobile): 

they are mounted to the door ends.

When type 2 safety ribbons operate during the gate opening
phase, the control unit will stand still immediately; when
type 2 safety ribbons operate during the gate closing, the
control unit will open the doors for 3 seconds, then it will
stand still. The direction of the gate at next command of
START or PEDESTRIAN START depends upon the parameter
STOP (it inverts or continues the motion). If the input STOP
is disabled, the command makes the motion continue in the
same direction. 

Both the input can manage the classic safety edge with n.c.
contact and the conductive rubber safety edge with 8,2 kohm
nominal resistance.

Connect type 1 safety ribbons cables between terminals 

J7 (EDGE1) 

and 

J9 (COM)

of the control unit.

Connect type 2 safety ribbons cables between terminals 

J8 (EDGE2) 

and 

J9 (COM)

of the control unit.

Summary of Contents for ALFARISS

Page 1: ...EUR ELECTROMECANIQUE 24V IRREVERSIBLE A CREMAILLERE POUR PORTAILS COULISSANTS JUSQU A 300 KG DE POIDS MOTOR ELECTROMECANICO 24V IRREVERSIBLES A CREMALLERA PARA PUERTAS CORREDERAS HASTA 300 KG DE PESO...

Page 2: ......

Page 3: ...34 4 2 ACTIVATION INPUTS 34 4 3 STOP 35 4 4 CONNECTING PHOTOCELLS 35 4 5 CONNECTING SAFETY RIBBONS 35 4 6 EXTERNAL AERIAL 36 4 7 LOW VOLTAGE LIGHT OUTPUT 36 4 8 COURTESY LIGHTS 36 4 9 POWER SUPPLY 36...

Page 4: ...y and hazard warnings on the machinery and equipment should be complied with Electromechanical actuators for gates are not intended to be used by people including children with diminished physical sen...

Page 5: ...t person The risk analysis should take into consideration all danger zones for the automation device which should be appropriately protected and marked In a clearly visible area apply a sign with info...

Page 6: ...50 Idling current A 0 9 Full load current A 3 Gate maximum speed m s 0 18 Maximum thrust N 330 Duty cycle 50 Pinion M4 Z16 Working temperature C 20 55 Motor weight Kg 7 5 Protection degree IP 44 Maxim...

Page 7: ...and parallel to the gate 5 Wait for the complete setting of the concrete 6 Unscrew the bolts fixing the base to the clamps and put the motor on the plate 7 Insert the 4 grains with their nuts in the p...

Page 8: ...gate making sure that they stand at the same height than the motor pinion The rack MUST BE positioned 1 or 2 mm over the pinion of the motor all the gate length 3 4 INSTALLING THE MAGNETIC LIMIT SWITC...

Page 9: ...restore the automation proceed as follows 1 Turn the key L anticlockwise until reached the limit switch then draw it out 2 Turn the key K anticlockwise closing the hatch of the lock then draw it out...

Page 10: ...rse the connectors 4 2 ACTIVATION INPUTS PD13 control unit is equipped with two activation inputs START and START P whose operation depends on the programmed operation modes see Strtitem of programmin...

Page 11: ...control unit Use outputs having normally closed contact mSAFETY RIBBONS INSTRUCTIONS If several edges with normally closed contacts are used the outputs should be connected in series If several conduc...

Page 12: ...VER PD13 control unit is suitable for plugging in a MRx receiver having a high sensitivity super heterodyne architecture MRx module receiver is provided with 4 channels and each of them is suitable fo...

Page 13: ...ing traditional devices with N O contact J2 Pedestrian open command for connecting traditional devices with N O contact J3 STOP command N C contact J4 Common J5 Photocell 1 xterior N C contact J6 Phot...

Page 14: ...explored by using the 3 keys h i and OK located on the side of the control unit display PLEASE NOTE Outside the configuration menu pressing the h key activates the START command pressing the i key ac...

Page 15: ...ges which will get lost 7 LOADING THE DEFAULT PARAMETERS dEF If necessary it is possible to restore all parameters to their standard or default values see the final summary table m PLEASE NOTE This pr...

Page 16: ...ached 5 2 The gate will be activated in opening direction until the stop end or the opening end of stroke is reached 5 3 The gate will be activated in closing direction until the stop end or the closi...

Page 17: ...cell edge limit switches or encoder To start the emergency dead man operating mode activate the start command START for 3 seconds Note if the Strt parameter is set as StAn the Start command from the t...

Page 18: ...eys you can alternate the display of thousands or units Area 2 is the reading of the number of cycles before the next request for service its value is rounded down to the hundreds Area 3 is the setup...

Page 19: ...unction This function is useful for reducing the energy consumption of the automation device while in stand by mode If the function is enabled the control unit will enter ENERGY SAVING mode under the...

Page 20: ...y of the obstacle sensor When the current absorbed by the motor exceeds the value set the control unit detects an alarm rA AP Slow down in opening 1 5 0 1 00 This menu allows regulating the percentage...

Page 21: ...the pause If the photocell operates during the opening time this time will be immediately stored as pause time This function allows having a fast closing as soon as transit through the gate is comple...

Page 22: ...rol unit ProS The input STOP stops the gate pressing the command START the gate continues the motion invE The command STOP stops the gate at the next START the gate starts moving in the opposite direc...

Page 23: ...reshold indicates the presence of an obstacle If set to 0 the obstacle is only detected when the gate is stopped When the sensor intervenes the gate stops and is operated in the reverse direction for...

Page 24: ...ed section 4 4 Error 4 When a Start command is given and the gate does not open or does a partial opening and the display shows Err4 It means that the end of stroke is damaged or that the wiring that...

Page 25: ...com 14 MAINTENANCE Maintenance should be performed in full compliance with the safety instructions described in this manual and in accordance with current legal and regulatory provisions The recommend...

Page 26: ...ENGLISH 50...

Page 27: ...months for normal domestic use but this period may vary depending on the intensity of use Any inspection maintenance or repairs should only be performed by qualified personnel Even if you think you kn...

Page 28: ...ENGLISH 52...

Page 29: ......

Reviews: