Service manual Platform 2014-2016, V-ZUG KT
1036497-00_ae gedruckt
7.10
Connecting solenoid valve
Connect capillary tube for main cooling compartment
(indicated in blue) and capillary tube for freezing
compartment to refrigerant valve, as shown in image
(capillary tube for main cooling compartment is shown on
left).
7.11
Replacing condenser
Caution!
Only carry out after cooling circuit has been
evacuated and flooded with nitrogen!
1.
Remove noise reduction element. Using soldering
flame, heat and release condenser connections.
Ensure no solder ingress into cold circuit.
(blockages)
2.
Remove screw connections on condenser.
3.
Screw on new condenser.
4.
Solder connections on compressor and frame
heater again.
Remove flux residue.
Put back noise reduction element.