(5) Clean the inverter cooling bin and fan with soft brush or vacuum cleaner.

(6) Install the screws and covers of cooling bin or fan box to their original place.

(7) Install the inverter to its original place again according to section installation.

(8) Repeat the operations in section inspection before operation.

(9) Restart the inverter.

FAN REPLACEMENT

If high temperature occurred to the inverter or abnormal noise occurred during fan 

rotating, replace the fan. Note that the fan should be replaced by professionals only.

How to replace the fan:

(1) Disconnect AC breaker;

(2) Turn the DC switch to “OFF” position;

(3) Wait for at least 10 minutes;

(4) Disconnect all the electrical wirings at the bottom of the inverter;

(5) Lift up the inverter with the help of others and take the inverter off the wall;

(6) Place the inverter on the operation platform;

(7) Disassemble the fan box as shown in Fig 21;

(8) Disassemble the damaged inverter fan as shown in Fig 22, then install the new fan 

back to its original position, and connect the fan power and control cable;

(9) Install the screws and covers of cooling bin or fan box to their original position;

(10) Install the inverter to its original position again according to section 4;

(11) Repeat the operations in section inspection before operation;

(12) Restart the inverter

 

 

Stop the inverter before maintenance operation, and disconnect all the power inputs 
of the inverter. 

 

Before carrying out maintenance operation, wait for at least 10 minutes until the 
internal capacitors of the inverter are fully discharged, 

 

The fan can be maintained and replaced by professional electricians only. 

 

Note

 

 

Do not start the inverter immediately if it alarms and stops. Figure out the cause 
according and confirm all the faults are removed before starting again. Inspections 
should be carried out in strict accordance with the procedures.

 

 

Figure 22 Replace the fan

Summary of Contents for VT-6605305

Page 1: ...BUL L KARAVELOW 9B 5 YEARS WARRANTY Thank you for selecting and buying V TAC Product V TAC will serve you the best Please read these instructions carefully keep this user manual handy for future refe...

Page 2: ...er people In order to avoid personal injury damage to the inverter or other devices please strictly observe the following safety precautions This chapter mainly describes various warning symbols in op...

Page 3: ...re is a danger of burning Do not touch It must be reliably grounded before operation Do not open the cover of inverters unauthorized The electrical parts and components inside the inverter are electro...

Page 4: ...es Only qualified electricians are allowed to install the inverter Do not put and install the inverter on or close to combustible materials Keep the installation site away from children and other publ...

Page 5: ...e local dealer or supplier for maintenance In order to avoid irrelevant personnel from entering the mainte nance area during maintenance temporary warning labels must be placed to warn non professiona...

Page 6: ...d connection When applied to the TT connection the N to PE voltage should be less than 30V Figure 2 Type of grid SUPPORTED GRID CONNECTION STRUCTURE PRODUCT APPEARANCE The recommended solar modules ne...

Page 7: ...e Instruction 1 Cover 2 Operational panel LED status light LCD display keypad 3 DC switch On off of the DC input optional 4 DC input port For the connection of solar modules 5 Communication port RS485...

Page 8: ...ctive EU WEEE mark Cannot dispose of the inverter as household waste Note The technical parameters of grid tied solar inverter refer to the appendix Product name Model Rated output power W Three phase...

Page 9: ...d net weight Figure 6 Paper packages dimension Table of packages dimension and gross weight Model H mm W mm D mm Net weight kg 5kW 530 360 150 20 8kW 10kW 575 360 150 23 W H D Model H mm W mm D mm Wei...

Page 10: ...les public grid and inverter Read this chapter carefully and ensure all installation requirements are met before installation Only quali ed electricians are allowed to install the inverter UNPACKING I...

Page 11: ...lts M5 20 2 5 Expansion bolts M6 50 4 6 Communication connector 1 7 DC connector 2 pairs 1pair 4kW S 5kW S 8 AC connector 1 No Installation tools Instruction 1 Marker Mark the installation hole 2 Elec...

Page 12: ...tal conductor should be consistent with the metal material reserved for the grounding of the inverter Install the inverter vertically or backward 15 to facilitate heat dissipation Do not tilt the inve...

Page 13: ...allation sites It is recommended to install the inverter vertically to the rm wall or metal bracket Here we take wall installation as an example to introduce the installation matters of the inverter A...

Page 14: ...in Figure 12 Inverter model Spacing of in allation hole A mm B mm 5kW 8kW 10kW 260 45 The procedures for installation of inverter are listed below 1 Use the punch positioning plate in the packaging bo...

Page 15: ...igure 13 5 Hang the inverter onto the installation bracket and ensure the installation is rm enough As shown in Figure 14 6 Ensure the inverter is installed properly and tighten the M5X20 bolts into t...

Page 16: ...juries or even death during system operation All the electrical installation must conform to the national and local electrical safety regulations Ensure all the cables are installed firmly according t...

Page 17: ...ctor is connected use a multimeter to measure the voltage of the DC input string verify the polarity of the DC input cable and ensure that the voltage of each string is within the allowable range of t...

Page 18: ...moving the DC connector from the inverter insert the head of the straight screwdriver into the raised hole in the middle of the connector and force the movable end of the connector to exit Figure 18 D...

Page 19: ...ction parameter settings to complete time setup 7 The default DC input mode of inverter is independent mode refer to section parameter settings to check and set DC input mode In order to ensure a safe...

Page 20: ...nto the file check the monitoring software and various parameter setup of the inverter Once per quarter Inverter running state Observe whether the inverter is installed firmly damaged or deformed List...

Page 21: ...ration operating content 5 Restart the inverter CLEAN THE FAN FOR 8KW AND 10KW INVERTER The cleaning steps are listed below 1 Disconnect the connection on input and output side 2 Wait for ten minutes...

Page 22: ...7 Disassemble the fan box as shown in Fig 21 8 Disassemble the damaged inverter fan as shown in Fig 22 then install the new fan back to its original position and connect the fan power and control cab...

Page 23: ...d state of inverter and LED indicators state LED indicator is off green yellow red LED indicator is blinking at every 0 25S or 0 5S Green yellow red LED indicator is on Table of inverter state and LED...

Page 24: ...t E001 Yellow indicator keeps on others off Unrecoverable fault Run Warn Fault Hardware or software fault E003 E004 E005 E008 E009 E011 E013 or E015 De couple the inverter from the system before maint...

Page 25: ...factory defaults Text Parameter Display Area Fault Code Status Area Figure 24 Main interface The main interface of the LCD screen is shown as the Figure 24 1 The curve displays the power changing at...

Page 26: ...s h p ri ce D at e T im e L an gu ag e Figure 29 Setting information H is to ry 0 2 01 2 0 1 0 5 1 1 3 2 1 6 A 0 05 G ri d un de r fr eq Historical record can display 32 pieces of historical informati...

Page 27: ...Setup menu can realize parameter setup shown in table of parameters setting LCD MENUS...

Page 28: ...LCD display Instruction RS485 Address R S 4 85 A dd re ss 0 01 1 Enter into the interface and edit the data through or And then press ENT again to the next bit After editing the three bits press ENT...

Page 29: ...e four bits press ENT to save the edition and press ESC to exit The currency types include EUR POD CNY and USD Setup Date Time S et up D at e T im e D at e 2 01 2 0 1 1 5 T im e 1 2 1 4 3 0 1 Enter in...

Page 30: ...ctor Limit Mode Invalid Invalid Auto Manual Limit Power 100 Power Factor Grid Tied Mode Normal Mode Power Factor 1 00 Input password 0000 The password is needed when enter into the interface of Set po...

Page 31: ...e 0 20s ACUFFreqency 47 6Hz ACUFTime 0 20s ACOFFreqency 51 4Hz ACOFTime 0 20s Inputpassword 0000 Password is required when enter into the interface of Run Param Get the password from the supplier if n...

Page 32: ...ACOF Time ACUV Volt phase volt ACUV Time ACOV Volt phase volt ACOV Time ACUF Frequency ACUF Time ACOF Frequency ACOF Time There are 2 protections under G83 G59 UK and PEA Thailand standards and there...

Page 33: ...ion interface to view the fault records Fault information records the latest 8 pieces of fault information of the inverter as shown in g 26 When there is no fault currently it will display No fault Se...

Page 34: ...ugh the panel And save the all settings and operation record Press ENT to ensure restarting and the inverter will begin to self inspect or press ESC to return Record clear C le ar a ll R ec or d S ur...

Page 35: ...Reference Table Grid certi cation and grid voltage and frequency of some countries...

Page 36: ...ss Keypad PWD C as h p ri ce D at e T im e L an gu ag e C ou nt ry Co un tr y C hi na Germany UK A us tr al ia G re ec e D en ma rk H ol la nd V pv1 000 0V I pv1 000 0A V pv2 000 0V 01 A001 MENU Alar...

Page 37: ...e of grid tied solar inverter is RS485 which includes RS485 M and RS485 S ports The RS485 M ports can communicate with private computers smart phones and so on The system monitoring solution is shown...

Page 38: ...cation devices nally transmitted to the monitoring system as standard Ethernet and WIFI signal Please download the connection instruction operation manual and commissioning tools on website Note the o...

Page 39: ...r PC A011 Grid Loss The public grid disconnects Check if inverter AC connection is well A030 Lost Box Box lost connection The communication is faulty between combiner box and inverter A031 BoxSPD1 Lig...

Page 40: ...7 safety E024 MeterLoss The smart meter not connected The smart meter not connected E025 Locking The inverter is locked The inverter is locked E026 Run Limit Light load Light load when anti feedback f...

Page 41: ...hers Input overvoltage protection input overcurrent protection DCisolation monitoring DCmonitoring grounding fault current monitoring grid monitoring island protection short circuit protection overhea...

Reviews: