CABLE SPECIFICATION
In order to regulate and compatible with the inverter AC/DC connector or terminal block
specifications, below requirements on the AC/DC cable connected to corresponding inverter
should be fulfilled:
MICRO BREAKER
In order to ensure safe operation of the inverter and circuits, it is recommended to
configure corresponding micro breaker or fuse on the DC input side and AC output side
of the inverter. Table below is the requirements recommended for micro breaker:
MECHANICAL INSTALLATION
The material for fixing the inverter and the installation mode vary with the different
installation sites. It is recommended to install the inverter vertically to the firm wall or
metal bracket. Here we take wall installation as an example to introduce the installation
matters of the inverter.
As shown in the Fig 10, the overall installation of the inverter should be vertical to the
horizontal surface.
Table of cable specifications
Table of specifications of micro breaker
Figure 10 Installation bracket of inverter
INSTALLATION OF INVERTER
Inverter model
DC side
AC side
Min cross-section
area
mm²
(length≤50m)
Min cross section
area mm²
(Length>50m)
Min cross section
areamm² (Length≤50m)
L
N/PE
5kW / 8kW / 10kW
4
6
4
4
Inverter model
DC side
AC side
Recommended breaker
specification
Recommended breaker
specification
5kW
DC1000V, C16A, 2P
AC400V, C16A, 4P
8kW / 10kW
DC1000V, C25A, 2P
AC400V, C25A, 4P