background image

VG-6132 Gas Extinguishing Panel   

 

(2)

 

Enter into  the standby state, check the power fault and operating  keys, as  well  as  field  devices  are  in 

good condition.   

4.5 Wiring 

After checking the control panel, if the results of all  the tests  meet the requirements, please refer to 

Chapter  3 

Structure

 in this  manual for connecting  terminals with field devices.  All cables should comply  with

 4.3 

Wiring 

Requirement

 

in this manual. 

4.6 Start 

Check AC input cable and make sure it is connected firmly. Then apply AC power, test the voltage. Switch on the 
power  after the voltage is  correct,  observe  LCD  and all  LEDs and ensure they  are  working  well. Switch off AC 
power immediately if there is any fault occurred and find out the reason. The panel can be restarted only after the 
fault is removed.   
If  there  isn’t  AC  power,  the  standby  power  is  only  used,  in  this  case,  press  the  Start  button  of  the  battery  after 
connection.   

4.7 Configure 

After check with the wiring and connection carefully, configure can be started according to the following steps.   

(1)

 

Switching  on  the  power,  the  control  panel  tests  LEDs,  LCD  and  sounds  automatically.  After  self-test,  the 

control panel enters the standby mode.   
(2)

 

Ensure the panel is placed in the clean air and then make commissioning. Refer to 

Chapter 5 System Setting 

and Operation

 and 

Chapter 6 Commissioning

 for details.   

Chapter 5 System Setting and Operation 

5.1 System Setup 

System setup mainly include system time set, delay set, loop check, printer set and so on. 

How to enter system setup: Switch on the power, press Menu to input “▲▼▲▼” password under system running 
screen, and then press “▼” to enter system setup screen.   

5.1.1 Time Set 

Go to 3 time set

. Press “Enter” key to go to system time set screen, shown as Fig. 5-1. 

 

 

 

Fig. 5-1 

Pressing    “Enter” key,    the cursor 

_

  will be switched. Pressing “▼” key, the number positioned at cursor, is 

added up 1 p. 
Pressing 

Enter

  saves the time after complete setting. Press Menu or Cancel to return.   

5.1.2 Delay Set 

Press “Menu” and type-in passwords. Then press “▼” key down to choose “4 Delay Set” and press “Enter” key to 
set delay time. 

 

 

 

 

Y:10  M:03 D:05 

15:18:58 

Zone 1 Delay 08 seconds 

Zone 2 Delay 18 seconds 

Summary of Contents for VG-6132

Page 1: ...VG 6132 Gas Extinguishing Panel Installation and Operation Manual Ver 1 02 October 2019 V GREAT GLOBAL CORPORATION...

Page 2: ...4 4 1 Unpacking and Inspecting 5 4 2 Installation 5 4 3 Wiring Requirements 5 4 4 Check of Control Panel 5 4 5 Wiring 6 4 6 Start 6 4 7 Configure 6 Chapter 5 System Setting and Operation 6 5 1 System...

Page 3: ...f the system It is easy and convenient to view the fire messages and status of the system from the LCD 2 1 2 Wiring The panel connects with external devices controlled through multi wire 2 2 Technical...

Page 4: ...ery Power On Abort 2 Auto Manual Standby Start 2 Start 1 Abort 1 Enter Reset Self test Silence Cancel Menu Power Fault Battery Fault COM Fault 430mm 330mm 106mm Fig 3 1 3 2 Installation Dimension Moun...

Page 5: ...Inspect Amber It turns on when the panel is under self testing Manual Red It turns on when Manual Auto lock is set to manual Auto Red It turns on when Manual Auto lock is set to auto Standby Red It t...

Page 6: ...Wiring description of terminal 1 is shown below Cylinder Cylinder Dete ction 1 Start Com Pressure Pressure Gas Release Gas Release Sounder 24V AC Panel Detection 1 Detection 2 Detection 2 Abort soleno...

Page 7: ...ires should be peeled 0 5cm and tinned or clipped before connecting into the cabinet Control Output Cable Conductor 1 0 mm2 or above copper conductor withstand voltage 250V twisted pair Cable 0 75 mm2...

Page 8: ...efully configure can be started according to the following steps 1 Switching on the power the control panel tests LEDs LCD and sounds automatically After self test the control panel enters the standby...

Page 9: ...t Press Menu key enter the password and then press key choose 8 Printer Set Press Enter key to go to the screen for setting printer as shown in Fig 5 2 Fig 5 3 Press key the printer can be set to ON o...

Page 10: ...Press to display fault messages It returns to fire condition if there is a fire Fig 6 2 5 6 2 History Record In system operation page press Menu and press to enter the screen shown as Fig 6 3 Then pre...

Page 11: ...2 If connected more than one Start Abort Button the end resistor must be installed on the last Start Abort Button 3 If the extinguishing panel was connected with Aerosol products or Electrical explos...

Page 12: ...1 The connection with display board is loose 2 CPU board is loose or mis placed 3 The panel crashes 4 Other reasons 1 Fasten the connector 2 Re start the control panel 3 Please contact with the manuf...

Page 13: ...he battery if it is placed for future use over three months We are responsible for repairing the control panel so please let us know if there is any problem Users are not allowed to disassembly or rep...

Reviews: