    3.5.2. Wiring description of terminal 2 is shown below.   
 

COM Fire

COM Fault

COM Start

COM Response

1 2 3 4 5 6 7 8

 

Notes

 

1. COM Fire, COM Start and COM Response are normally closed, and    open when activated.   
2. COM Fault is normally open and closed when activated.   

Chapter 4 Installation and Commissioning 

4.1 Unpacking and Inspecting 

Open  the  package  carefully  not  to  damage  the  control  panel.  Check  the  items  against  the  packing  list.  Check 
internal  configuration  and  connection  of  different  parts.  Then  inspect  the  appearance  of  the  control  panel.  If  a 
problem is found, solve it as soon as possible and then install the control panel.   

4.2 Installation   

Mounting dimension is shown as Fig. 3-2.   

4.3 Wiring Requirements 

◇ 

Wiring  for  terminals  inside  the  cabinet:  all  wires  should  be  peeled  0.5cm  and  tinned  or  clipped  before 

connecting into the cabinet. 

◇ 

Control Output Cable:   
Conductor

1.0 mm

or above copper conductor, withstand voltage≥ 250V

twisted pair.   

Cable

0.75 mm

or above copper cable

withstand voltage≥ 250V.   

Total resistance of cable

50Ω

otherwise increase the cross section of the cable.   

◇ 

Conduit Pipe: The cable should be installed in a individual conduit pipe, and be away from others cables such 

as power line, lighting cable, AC cable, CCTV cable, VA cable etc. 

◇ 

Wiring in cable shaft: The loop wires should be installed in a respective metal sink, away from those wires 

such as power line, lighting cable, CCTV cable etc, the parallel distance between    the loop wite and other power 
supply lines should be further than 500mm. 

◇ 

Connectors:  all  connectors  for  wiring  should  be  welded  or  crimped  and  sealed  by  isolated  sleeves  to  avoid 

short circuit and current leaking. 

4.4 Check of Control Panel 

When the control panel is installed in the field, turns on the power and do the functional checks at first, including

 

(1)

 

Observe if the LEDs and sections of LCDs are lit and the loudspeaker gives a resonant sound. 

Summary of Contents for VG-6132

Page 1: ...VG 6132 Gas Extinguishing Panel Installation and Operation Manual Ver 1 02 October 2019 V GREAT GLOBAL CORPORATION...

Page 2: ...4 4 1 Unpacking and Inspecting 5 4 2 Installation 5 4 3 Wiring Requirements 5 4 4 Check of Control Panel 5 4 5 Wiring 6 4 6 Start 6 4 7 Configure 6 Chapter 5 System Setting and Operation 6 5 1 System...

Page 3: ...f the system It is easy and convenient to view the fire messages and status of the system from the LCD 2 1 2 Wiring The panel connects with external devices controlled through multi wire 2 2 Technical...

Page 4: ...ery Power On Abort 2 Auto Manual Standby Start 2 Start 1 Abort 1 Enter Reset Self test Silence Cancel Menu Power Fault Battery Fault COM Fault 430mm 330mm 106mm Fig 3 1 3 2 Installation Dimension Moun...

Page 5: ...Inspect Amber It turns on when the panel is under self testing Manual Red It turns on when Manual Auto lock is set to manual Auto Red It turns on when Manual Auto lock is set to auto Standby Red It t...

Page 6: ...Wiring description of terminal 1 is shown below Cylinder Cylinder Dete ction 1 Start Com Pressure Pressure Gas Release Gas Release Sounder 24V AC Panel Detection 1 Detection 2 Detection 2 Abort soleno...

Page 7: ...ires should be peeled 0 5cm and tinned or clipped before connecting into the cabinet Control Output Cable Conductor 1 0 mm2 or above copper conductor withstand voltage 250V twisted pair Cable 0 75 mm2...

Page 8: ...efully configure can be started according to the following steps 1 Switching on the power the control panel tests LEDs LCD and sounds automatically After self test the control panel enters the standby...

Page 9: ...t Press Menu key enter the password and then press key choose 8 Printer Set Press Enter key to go to the screen for setting printer as shown in Fig 5 2 Fig 5 3 Press key the printer can be set to ON o...

Page 10: ...Press to display fault messages It returns to fire condition if there is a fire Fig 6 2 5 6 2 History Record In system operation page press Menu and press to enter the screen shown as Fig 6 3 Then pre...

Page 11: ...2 If connected more than one Start Abort Button the end resistor must be installed on the last Start Abort Button 3 If the extinguishing panel was connected with Aerosol products or Electrical explos...

Page 12: ...1 The connection with display board is loose 2 CPU board is loose or mis placed 3 The panel crashes 4 Other reasons 1 Fasten the connector 2 Re start the control panel 3 Please contact with the manuf...

Page 13: ...he battery if it is placed for future use over three months We are responsible for repairing the control panel so please let us know if there is any problem Users are not allowed to disassembly or rep...