Chapter 6 Commissioning 

6.1 Commissioning notes 

1. Before commissioning works, please take off the wires, and use the Multimeter to test the resistance value 

of cables at first. The resistance of all wires should be over 4.7 k

Ω

2. If connected more than one Start/Abort Button, the end resistor must be installed on the last Start/Abort 

Button. 
 

3. If the extinguishing panel was connected with Aerosol products or Electrical-explosion initiator, please set 

the Jumper P4 and P5 same as the Pic 6-1 shown.   

                                           

 

Pic 6-1 

4. In some projects with special requirements, if the function of loop testing for short or open circuit is not 

required, please turn the switch to the right side as Pic 6-2 shown.   

Summary of Contents for VG-6132

Page 1: ...VG 6132 Gas Extinguishing Panel Installation and Operation Manual Ver 1 02 October 2019 V GREAT GLOBAL CORPORATION...

Page 2: ...4 4 1 Unpacking and Inspecting 5 4 2 Installation 5 4 3 Wiring Requirements 5 4 4 Check of Control Panel 5 4 5 Wiring 6 4 6 Start 6 4 7 Configure 6 Chapter 5 System Setting and Operation 6 5 1 System...

Page 3: ...f the system It is easy and convenient to view the fire messages and status of the system from the LCD 2 1 2 Wiring The panel connects with external devices controlled through multi wire 2 2 Technical...

Page 4: ...ery Power On Abort 2 Auto Manual Standby Start 2 Start 1 Abort 1 Enter Reset Self test Silence Cancel Menu Power Fault Battery Fault COM Fault 430mm 330mm 106mm Fig 3 1 3 2 Installation Dimension Moun...

Page 5: ...Inspect Amber It turns on when the panel is under self testing Manual Red It turns on when Manual Auto lock is set to manual Auto Red It turns on when Manual Auto lock is set to auto Standby Red It t...

Page 6: ...Wiring description of terminal 1 is shown below Cylinder Cylinder Dete ction 1 Start Com Pressure Pressure Gas Release Gas Release Sounder 24V AC Panel Detection 1 Detection 2 Detection 2 Abort soleno...

Page 7: ...ires should be peeled 0 5cm and tinned or clipped before connecting into the cabinet Control Output Cable Conductor 1 0 mm2 or above copper conductor withstand voltage 250V twisted pair Cable 0 75 mm2...

Page 8: ...efully configure can be started according to the following steps 1 Switching on the power the control panel tests LEDs LCD and sounds automatically After self test the control panel enters the standby...

Page 9: ...t Press Menu key enter the password and then press key choose 8 Printer Set Press Enter key to go to the screen for setting printer as shown in Fig 5 2 Fig 5 3 Press key the printer can be set to ON o...

Page 10: ...Press to display fault messages It returns to fire condition if there is a fire Fig 6 2 5 6 2 History Record In system operation page press Menu and press to enter the screen shown as Fig 6 3 Then pre...

Page 11: ...2 If connected more than one Start Abort Button the end resistor must be installed on the last Start Abort Button 3 If the extinguishing panel was connected with Aerosol products or Electrical explos...

Page 12: ...1 The connection with display board is loose 2 CPU board is loose or mis placed 3 The panel crashes 4 Other reasons 1 Fasten the connector 2 Re start the control panel 3 Please contact with the manuf...

Page 13: ...he battery if it is placed for future use over three months We are responsible for repairing the control panel so please let us know if there is any problem Users are not allowed to disassembly or rep...

Reviews: