Critical status of VG-6132 Gas Extinguishing Panel are indicated by LEDs, description is shown as below.     
Main control    section 

 

Power

Green

It  turns  on  when  the  main  power  is  supplied  and  turns  off  when  the  power  is  low 

voltage or the power cable is broken.   

 

Battery

Green

It  turns  on  when  the    battery  power  is  working  normally,  and  turns  off  when  the 

battery power is low voltage or the power cable is broken.   

 

Silence

Green

  The LED turns on when the Silence key is pressed.Reserve

Amber

LED Reserve 

for other usage.   

 

Power Fault

Amber

It turns on when the main power is low voltage or the cable is broken, and turns 

off when the main power is working normally.   

 

Batt Fault

Amber

It turns on when the standby power is low voltage or the cable is broken and turns 

off when the standby power is working normally.   

 

COM Fault

Amber

It runs on when there is any fault occurred on the control panel and turns off when 

all faults are removed.   

 

SYS Inspect

Amber

It turns on when the panel is under self-testing. 

 

Manual

Red

It turns on when Manual/Auto lock is set to manual.   

 

Auto

Red

It turns on when Manual/Auto lock is set to auto.   

 

Standby

Red

It turns on when Override lock is closed.   

 

Override

Red

It turns on when Override lock is opened.   

Fire Protection Zone Section 

 

Pre-alarm

Red

It turns on when there is fire and turns off automatically if there is no fire alarm within 

30 minutes. 

 

Fire 

Red

It turns on when there is fire and turns off automatically if there is no alert signal within 30 

minutes. 

 

Activate

Red

In AUTO mode, LED turns on when the panel activates the action outputs. 

 

Sounder

Red

It turns on when the sounder strobe is activated and turns off when the sounder strobe is 

off.   

 

Delay

Red

It turns on when the panel is in delay mode.   

 

Discharge

Red

It turns on when the control panel activates the cylinder valve.     

 

Response

Red

):

It  turns  on  when  the  panel  receiving  feedback  from  solenoid  valve,  and  LED 

illuminates until reset.   

 

Start

Red

It turns on when the Start button is pressed and turns off whenthe Abort button is pressed.   

 

Abort

Red

It turns on when the Abort button is pressed and turns off after reset.   

Summary of Contents for VG-6132

Page 1: ...VG 6132 Gas Extinguishing Panel Installation and Operation Manual Ver 1 02 October 2019 V GREAT GLOBAL CORPORATION...

Page 2: ...4 4 1 Unpacking and Inspecting 5 4 2 Installation 5 4 3 Wiring Requirements 5 4 4 Check of Control Panel 5 4 5 Wiring 6 4 6 Start 6 4 7 Configure 6 Chapter 5 System Setting and Operation 6 5 1 System...

Page 3: ...f the system It is easy and convenient to view the fire messages and status of the system from the LCD 2 1 2 Wiring The panel connects with external devices controlled through multi wire 2 2 Technical...

Page 4: ...ery Power On Abort 2 Auto Manual Standby Start 2 Start 1 Abort 1 Enter Reset Self test Silence Cancel Menu Power Fault Battery Fault COM Fault 430mm 330mm 106mm Fig 3 1 3 2 Installation Dimension Moun...

Page 5: ...Inspect Amber It turns on when the panel is under self testing Manual Red It turns on when Manual Auto lock is set to manual Auto Red It turns on when Manual Auto lock is set to auto Standby Red It t...

Page 6: ...Wiring description of terminal 1 is shown below Cylinder Cylinder Dete ction 1 Start Com Pressure Pressure Gas Release Gas Release Sounder 24V AC Panel Detection 1 Detection 2 Detection 2 Abort soleno...

Page 7: ...ires should be peeled 0 5cm and tinned or clipped before connecting into the cabinet Control Output Cable Conductor 1 0 mm2 or above copper conductor withstand voltage 250V twisted pair Cable 0 75 mm2...

Page 8: ...efully configure can be started according to the following steps 1 Switching on the power the control panel tests LEDs LCD and sounds automatically After self test the control panel enters the standby...

Page 9: ...t Press Menu key enter the password and then press key choose 8 Printer Set Press Enter key to go to the screen for setting printer as shown in Fig 5 2 Fig 5 3 Press key the printer can be set to ON o...

Page 10: ...Press to display fault messages It returns to fire condition if there is a fire Fig 6 2 5 6 2 History Record In system operation page press Menu and press to enter the screen shown as Fig 6 3 Then pre...

Page 11: ...2 If connected more than one Start Abort Button the end resistor must be installed on the last Start Abort Button 3 If the extinguishing panel was connected with Aerosol products or Electrical explos...

Page 12: ...1 The connection with display board is loose 2 CPU board is loose or mis placed 3 The panel crashes 4 Other reasons 1 Fasten the connector 2 Re start the control panel 3 Please contact with the manuf...

Page 13: ...he battery if it is placed for future use over three months We are responsible for repairing the control panel so please let us know if there is any problem Users are not allowed to disassembly or rep...