![V-GREAT VG-6132 Installation And Operation Manual Download Page 5](http://html1.mh-extra.com/html/v-great/vg-6132/vg-6132_installation-and-operation-manual_3077812005.webp)
VG-6132 Gas Extinguishing Panel
3
Fig. 3-3
Critical status of VG-6132 Gas Extinguishing Panel are indicated by LEDs, description is shown as below.
Main control section
◇
Power
(
Green
)
:
It turns on when the main power is supplied and turns off when the power is low
voltage or the power cable is broken.
◇
Battery
(
Green
)
:
It turns on when the battery power is working normally, and turns off when the
battery power is low voltage or the power cable is broken.
◇
Silence
(
Green
)
:
The LED turns on when the Silence key is pressed.Reserve
(
Amber
)
:
LED Reserve
for other usage.
◇
Power Fault
(
Amber
)
:
It turns on when the main power is low voltage or the cable is broken, and turns
off when the main power is working normally.
◇
Batt Fault
(
Amber
)
:
It turns on when the standby power is low voltage or the cable is broken and turns
off when the standby power is working normally.
◇
COM Fault
(
Amber
)
:
It runs on when there is any fault occurred on the control panel and turns off when
all faults are removed.
◇
SYS Inspect
(
Amber
)
:
It turns on when the panel is under self-testing.
◇
Manual
(
Red
)
:
It turns on when Manual/Auto lock is set to manual.
◇
Auto
(
Red
)
:
It turns on when Manual/Auto lock is set to auto.
◇
Standby
(
Red
)
:
It turns on when Override lock is closed.
◇
Override
(
Red
)
:
It turns on when Override lock is opened.
Fire Protection Zone Section
◇
Pre-alarm
(
Red
)
:
It turns on when there is fire and turns off automatically if there is no fire alarm within
30 minutes.
◇
Fire
(
Red
)
:
It turns on when there is fire and turns off automatically if there is no alert signal within 30
minutes.
◇
Activate
(
Red
)
:
In AUTO mode, LED turns on when the panel activates the action outputs.
◇
Sounder
(
Red
)
:
It turns on when the sounder strobe is activated and turns off when the sounder strobe is
off.
◇
Delay
(
Red
)
:
It turns on when the panel is in delay mode.
◇
Discharge
(
Red
)
:
It turns on when the control panel activates the cylinder valve.
◇
Response
(
Red
):
It turns on when the panel receiving feedback from solenoid valve, and LED
illuminates until reset.
◇
Start
(
Red
)
:
It turns on when the Start button is pressed and turns off whenthe Abort button is pressed.
◇
Abort
(
Red
)
:
It turns on when the Abort button is pressed and turns off after reset.