Level limit switch
Series RF 3000
Technical Information / Instruction manual
page
General Safety Instructions
Process
pressure
Improper installation may result in loss of process pressure.
Seal the process thread with PTFE sealing tape in case of process pressure
A plastic sealing must be used to tighten the flange.
Fastening of the
threaded process
connection
Mounting torque for the thread may not exceed 80 Nm. Use a fitting open-end wrench. Do not fasten by
turning the housing.
Sliding sleeve: Tighten both straining screws M8 with 20 Nm to obtain resistance against pressure.
Precaution for later
dismounting/ Service
Grease the screws of the lid if corrosive atmosphere is present (e.g. close to sea)
Direction of the cable
glands
When the unit is mounted from the side, ensure, that the cable glands faces downwards and are closed
to avoid water penetration into the housing. The housing can be rotated against the process connection
after mounting.
Chemical resistance
against the medium
Materials of construction are chosen based on their chemical compatibility (or inertness) for general
purposes. For exposure to specific environments, check with chemical compatibility charts before
installing.
Temperature range
The range of the ambient and process temperature of the device must be observed.
Mechanical load
The rated values must not be exceeded.
EHEDG/ Food grade
material
The materials are available for the use under normal and predictable applications (according to
directive 1935/2004 Art.3). Other conditions can influence the safety.
Mounting
Additional Safety Instructions for Hazardous Locations
Installation regulations
For devices to use in hazardous locations the respectively valid installation regulations must be
observed.
Sparks
The installation has to be done in a way mechanical friction or impact can not cause sparks between
the aluminium enclosure and steel.
Weather protection
cover
The weather protection cover is approved for Zone 2, 22 and Div.2
RFnivo
®
1
2
3
4
5
6
7
8
9
10
11
12
RF 3000 f
gi241014
14