Level limit switch
Series RF 3000
Technical Information / Instruction manual
page
Notes for use in Hazardous Locations
Zone classification
usable in zone
Category
Equipement
Protection
Level (EPL)
Dust applications 20, 21, 22
1 D
Da
21, 22
2 D
Db
22
3 D *
Dc
Gas applications
0, 1, 2
1 G
Ga
1, 2
2 G
Gb
2
3 G
Gc
General Notes
* in case of conductive dust additional
requirements for the installation may
be necessary.
Marking
Devices with Ex approval are marked on name plate.
Process pressure
Devices with Ex Approval are approved for atmospheric pressure.
A detailed explanation is given below for ATEX and applies analogously for other Ex approvals:
The scope of the ATEX directive is generally limited to atmospheric pressure, see ATEX directive
2014_34_EU Chapter 1 Art.2 (4).
Atmospheric pressure is defined as absolute pressure 0.8bar to 1.1bar, see ATEX guideline §50 and IEC
60079-0 chapter 1 Scope.
The technical background is that an explosive atmosphere which is compressed (overpressure) or
released (underpressure) can exhibit different explosion behaviour than under atmospheric conditions.
The standards for the types of protection against explosion (IEC 60079 series), on which a type
approval according to the ATEX directive is based, are designed for atmospheric conditions and do not
automatically cover deviating pressure conditions.
Thus, an ATEX type approval issued in accordance with this directive only covers atmospheric
pressure.
This applies to all manufacturers.
A deviating operating pressure can be assessed and approved by an expert for the respective
application.
Regardless of this, the design of the level indicators is suitable for a vessel overpressure /
underpressure in accordance with the specified technical data.
Process and ambient
temperature
The permitted temperature ranges are marked on the name plate.
The max. permitted ambient and process temperatures (including temperature derating) stated in this
manual must be observed.
Electrostatic charge
The apparatus shall be installed in way that danger caused by electrostatic charges is avoided.
Flameproof joints
The flameproof joints are not intended to be repaired.
Remote version
Potential equalization must exist along the intrinsically safe circuit between the electronics enclosure and
the probe.
Specific condition of use
Year of manufacturing
2018 2019 2020 2021 2022 2023 2024 2025 2026 2027 2028 2029
Marking code
K
L
M
N
P
R
S
T
U
V
W
X
ATEX: Year of manufacturing
Marking on the name plate is done according to IEC 60062 as follows:
RFnivo
®
1
2
3
4
5
6
7
8
9
10
11
12
RF 3000 f
gi241014