Level limit switch
Series RF 3000
Technical Information / Instruction manual
page
1.
Open the housing lid
2.
Remove the field wiring cables
3.
Remove the two fastening screws
4.
Take out the electronic board, remove cable ties and internal wires
5.
Mount a new electronic board in reverse sequence
CAUTION:
•
Observe right sequence of internal probe wires
•
Obeserve to reconnect the internal grounding wire
•
Opening the lid (cover): see safety notes on page before
•
Hazardous Locations: The unit must have always an electronic board inserted and conneted to the probe. If the
electronic board is not connected to the probe, the probe acts as an isolated capacitance. The risk of static charge
and thus possible explosion is present.
Change of electronic board
Electronic
(view from
below)
Internal
probe
wires
Cover plate
Internal
grounding
wire
Fastening
screw
Fastening
screw
Cable tie
Maintenance
RFnivo
®
1
2
3
4
5
6
7
8
9
10
11
12
RF 3000 f
gi241014
40