Hallett 15xs Instruction Manual
Released on 11-Jul-13 – H800003Q
Page 21
UV Pure Technologies Inc. © 2013
full power or the unit is in standby mode awaiting a remote start.
Amber Light – situated in the middle, an illuminated amber light may indicate the
Initial Set-up process has begun or a warning of some condition that, if not
addressed, could impact the Hallett’s performance. Warnings should be
addressed as soon as possible. Warnings are accompanied with a single beep,
messages and troubleshooting tips on the LCD display.
Red Light – situated at the top, an illuminated red light indicates an alarm which
has significantly impacted the Hallett’s performance and it must be addressed
immediately. Alarms are accompanied with continuous beeping, messages and
troubleshooting tips on the LCD display.
Audio Alarm
The audio alarm or beeper, will alert the operator to any conditions out of the
ordinary, A single beep will sound if a warning occurs; continuous beeping will
sound if an alarm occurs – see Menu & Troubleshooting Section for more details
on warning and alarms. The audio alarm may be disabled temporarily or
permanently in the Service Menu.
Starting the Unit
Caution: Do not operate unit with the front panel or ballast enclosure door
open. Do not try to open the front panel or ballast enclosure door when the
unit is operating
– Shutdown and unplug the unit first before trying to gain
access. The Hallett contains a safety switch that will disable the lamp power
supply (ballast) if the front panel is not completely closed.
Caution
: Avoid continuously starting and stopping the unit within a 24 hr period,
as this will accelerate the aging of the UV lamps (note: however shutting down
the system for seasonal use will extend lamp life)
Caution: Do not operate unit dry.
There must be water in the treatment
chamber to prevent damage to internal components. In the event of a lack of
water or water supply being turned off, shutdown the unit until the water supply
can be restored. In the event of a power failure, the unit will shut down and the
solenoid valve will close, preventing water from flowing. When the power returns,
the unit will automatically restart and perform a self-test. If no faults are detected,
the unit will return to normal operation and the solenoid valve will open. Note that
even during a brownout, the supply voltage may drop low enough to cause the
unit to shut down. If the unit does not automatically restart as described above,
shutdown and unplug the unit and plug it in again.
Step 1:
Plug the unit into the Transient Voltage Surge Suppressor, and plug the
Transient Voltage Surge Suppressor into a grounded outlet to start the unit.
Caution:
Never look into or place any exposed skin into the illuminated areas
when the unit is operating.
Step 2:
Once the unit is plugged in, all three lights will illuminate an audible
alarm will sound and the display will become active. This verifies that the lights
and the audible alarm are functioning. The unit then performs a self-test. When