Accuriss Communications
Communications to the Accuriss is possible with any RS485 compatible communication device
and any commonly available terminal program. Most computers have either an RS232 or USB
port (sometimes both). USAutomation offers software drivers for both on our web site or in our
Starter Kit. Commercially available USB to RS485 and RS232 to RS485 converters will allow
communications with the Accuriss from most computers using only a compatible terminal
program.
Also available as a software tool is the Accuriss Terminal software, which is available as a no
charge download from our web site, or it is included in our Starter Kit.
Communication Specifications
Electrical
Characteristics
In conformance with EIA-485 Use a twisted pair cable (TIA/EIA-568B CAT5e or
higher is recommended) and keep the total wiring distance including extension to
50 m (164 ft.) or less.
Baud rate
Selectable from 9570 bps, 19200 bps, 38400 bps (9570 is default)
Physical layer
Asynchronous mode (8 bits, 1 stop bit, no parity)
Starter Kit
The Accuriss Starter Kit is recommended for any first time user of the Accuriss 57. This kit
contains a USB to RS485 converter, an I/O break out board, two input switches, and a CD that