background image

P9

Care iS required for shutters with mechanical limit switches: 

do not power up if the shutter is completely closed.

Position the shutter mid-way using the opening and closing wires before powering up the module.

The module will adapt 

automatically

to the various types of shutters with electronic, electrical, or mechanical limit switches.

Motor operation is always limited to 90 seconds, except in the case of the electronic limit switches: in this case the operation

is limited to 40 seconds. Installers may change this type from 5 seconds (minimum) to infinite by using the electronic limit

switches  (contact  our  Customer  Care  if  necessary).  Code  24  followed  by  code  26  allows  the  motor  contact  timing  to  be

deactivated.

POWER-UP

1.   use of the module

The MVR500MRP(X) may be controlled by a single or double (not interlocked) pushbutton. The shutter reacts within a few

tenths of a second after pressing the pushbutton.

With single pushbutton: press once to open or close the shutter completely. Press again while the shutter is moving to stop

it.  In  this  case,  the  module  will  invert  the  direction  of  the  movement  the  next  time  the  pushbutton  is  pressed.

With the double pushbutton (not interlocked): (use of the accessory Yokis R12M Mod: 5454073 is required). Press the up

pushbutton to open and stop opening. Press the down pushbutton to close and stop closing. While closing, pressing the up

pushbutton will cause a 0.5 second stop before opening. Pressing both pushbuttons at the same time will open the shutter.

With remote control: As in the single pushbutton operation. Refer to the remote control instruction manual.

Short presses

: Yokis modules can be used or configured by means of sequences of short presses. The speed must be at

least two presses per second. The shutter will not move during the press sequence. The shutter will confirm the configuration

with a short up and down movement at the end of the press sequence. If several modules have to be configured identically,

the short press method may be used on the centralised pushbutton or, in the case of double centralised pushbuttons,–either

on the up or down pushbutton.

iMPortaNt: unlock the module with a 23 short presses sequence before starting to configure it.

2.   intermediate position

An Intermediate position can be configured (for example: with the slats open). In order to do this, close the shutter completely

and then open it to the desired Intermediate position. 

5

short presses will memorise the position. From this moment on, 

2

short

presses will take the shutter to the previously stored position from any current position (closed, open, or in between).

3.   daily scheduler

The daily scheduler makes it possible to open and close the shutter at set times. The MVR500MRP(X) has an internal 24-hour

clock.  This clock does not need to be adjusted.

Daily scheduling of the closing time: 

8

short presses performed at the time of the day at which you want to close the shutter.

Daily scheduling of the opening time: 

9

short presses performed at the time of the day at which you want to open the shutter.

Daily scheduling of the intermediate position: 

7

short presses performed at the time of the day at which you want to leave the

shutter in an intermediate position.

10

short presses deletes all scheduling.

Example:

8

short presses at 9:30 p.m. are sufficient to close the shutters every day at that time.

Note: The MVR500M will clear all daily scheduling if power is disconnected or in case of blackout. In these cases, the scheduled

times will need to be reprogrammed. As an alternative, an external timer switch or dusk sensor may be connected by the CVI34

accessory (Code 5454806).

22

short presses will 

deactivate the possibility of setting daily schedules

. The user can no longer schedule daily opening,

closing, or intermediate position operations (this is recommended for installations in the service sector). 

4.   restoring default settings

25

short presses will restore the default settings. The module will perform the following actions in sequence: delete all daily

scheduling, delete the electronic limit switches, enable inverted movement in case of overload, set motor torque to low, delete

up and down wire logic reversal, enable daily scheduling, enable limit switch and motor torque control.

5.   How to block the module

The configuration block prevents accidentally changing the module settings in case of repeated presses. The module is not

blocked when it leaves the factory. 

21

short presses block the module. The module will no longer respond to configurations

made using the short presses sequence from 12 to 26. An exception is the 

23

short presses sequence, which allows to remove

the block. The module will respond again to configurations set using the short presses sequences from 12 to 26.

OPERATION

DS1054-025B

urmet S.p.a. – 10154 toriNo (itaLY) – Via Bologna 188/C

For technical information, go to www.yokis.com or call: 

Customer Service: +39 011.23.39.810 -  export dept. Phone: +39 011.24.00.250/256 -

Fax: +39 011.24.00.296

DS1054-025B_A5  01/02/2017  10:21  Pagina 9

Summary of Contents for 5454469

Page 1: ...MVR500MRP X Si elle est sup rieure 20V ins rer une D600V entre les fils retour du BP et la borne BP fil blanc sur la borne BP 3 Brancher les fils du moteur sur les bornes 3 4 et 6 V rifier que le fil...

Page 2: ...etteur clignote faire un appui court avec la pointe d un stylo dans le trou connect du r cepteur r situ en fa ade du bo tier La led de l metteur s arr te de clignoter Attention il faut que le r cepteu...

Page 3: ...10 appuis courts Exemple Pour fermer quotidiennement vos volets 21H30 il suffit cette heure ci de faire 8 appuis courts NB En cas de coupure secteur le MVR500 annule toutes les programmations journali...

Page 4: ...ons rapides sur une touche de l metteur MENU R glages La led de l metteur se met alors clignoter rapidement 2 Pendant que la led clignote faire 10 impulsions rapides sur la touche de l metteur passer...

Page 5: ...mentazione dei moduli deve essere la stessa del filo pilota Degli schemi d impianto sono disponibili presso la nostra assistenza tecnica per il cablaggio in impianti trifase 1 Connettere l alimentazio...

Page 6: ...e intermedia ad es con le lamelle scostate Per far ci chiudere completamente la tapparella e poi aprirla alla posizione intermedia desiderata Fare 5 pressioni corte per memorizzare la posizione Da que...

Page 7: ...uso cui destinato La difettosit non dovr essere stata causata da un deterioramento o da un incidente risultante da negligenza utilizzo anomalo o montaggio inadeguato In ogni caso la garanzia non copr...

Page 8: ...humidity from 0 to 70 Module consumption 0 77W 3 2VA radio frequency 2 4GHz dimensions 90 x 17 5 x 60 mm 3 54 x 0 68 x 2 36 GB The module must be installed only by qualified personnel and into a place...

Page 9: ...ermediate position 5 short presses will memorise the position From this moment on 2 short presses will take the shutter to the previously stored position from any current position closed open or in be...

Page 10: ...the date of manufacture The material must be used according to the instructions provided and for its intended use Faults must not be caused by deterioration or accidents resulting from negligence ano...

Page 11: ...lativa del 0 al 70 Consumo del m dulo 0 77 W 3 2 VA Frecuencia radio 2 4 GHz dimensiones 90 x 17 5 x 60 mm DS1054 025B eS El m dulo debe instalarse exclusivamente por personal calificado y en un lugar...

Page 12: ...alizar 5 pulsaciones breves para memorizar la posici n A partir de ese momento con la persiana cerrada abierta o en cualquier otra posici n ser posible realizar 2 pulsaciones breves para llevarla a la...

Page 13: ...orme a las prescripciones indicadas y al uso al que est destinado El defecto no debe haber sido provocado por un deterioro o por un accidente causado por negligencia uso anormal o montaje inadecuado E...

Page 14: ...s tasters und der Klemme BP des MVr500MrP X verwenden und dabei darauf achten den wei en Leiter des d600V an die Klemme BP anzuschlie en 3 Die Leiter des Motors an die Klemmen 3 4 und 6 Schlie en ansc...

Page 15: ...ann in der gew nschten Zwischenposition ge ffnet werden Durch 5 maliges kurzes Dr cken wird die Position gespeichert Ab diesem Moment ist es bei geschlossenem oder ge ffnetem Rollladen oder aus jeder...

Page 16: ...dieses Produkt eine Garantie von 5 Jahren ab Herstellungsdatum Das Material muss im Einklang mit den angegebenen Vorschriften und bestimmungsgem verwendet werden Defekte d rfen nicht durch eine Besch...

Page 17: ...veiligheidsnormen te voldoen moet de module worden aangesloten op een beveiligde elektriciteitsleiding na een veiligheidsschakelaar van 10A in curve C Voer de bedrading van de module uitsluitend uit...

Page 18: ...rst het rolluik volledig en laat het dan opengaan tot op de gewenste tussenstand Druk 5 keer snel op de knop om deze stand op te slaan Vanaf dit ogenblik kunt u een rolluik dat open of gesloten is of...

Page 19: ...elde voorschriften en de voorziene gebruiksdoeleinden Defecten mogen niet veroorzaakt zijn door slijtage of ongevallen als gevolg van nalatigheid niet voorziene aanwending of verkeerde montage In elk...

Page 20: ...rmity is available at the following internet address www Yokis com eSPa oL deCLaraCi N ue de CoNForMidad SiMPLiFiCada Por la presente Yokis S a s declara que los tipos de equipos radioel ctricos M dul...

Reviews: