Heating and cooling system
Option 3
230 V
Option 1
Move PLUS
Move
Move PLUS
Option 2
N OT E !
This is an outline diagram. A real system must
be installed according to applicable norms
and regulations.
N OT E !
If the outdoor sensor is placed to far away
from the reference room (Move PLUS only),
a separate thermostat can be used to register
the outdoor sensor.
N OT E !
When registering a thermostat to the
controller (Move PLUS only), run mode
changes parameter
0 (type)
to
rEv
,
regardless of previous setting. Heating/
cooling is then controlled by the thermostat,
or the integrated system.
Warning!
There is 230 V (5 A) power in the controller
when connected to the mains.
This installation example depicts a heating and cooling
system.
The circulation pump and mixer valve is operated by the
controller to maintain the supply temperature.
The controller switches between heating and cooling
using either a physical heating/cooling switch
(option 1) connected to the controller, or via a digital
thermostat (Move PLUS only). These options cannot
be combined in a Move PLUS system, since the
HC
option in parameter 11, or 12, is disabled when a digital
thermostat is registered to the controller.
An optional switchover valve (option 2) can be used
to divert the supply between the heating and cooling
sources.
An optional return temperature sensor (option 3), is
in a Move system connected the controller to speed
up the reaction of the system. This is achieved using
a boost parameter to adjust the calculated supply
temperature, if the difference between supply and
return temperatures is to large.
Example specific electrical connections
• The circulation pump is connected to the terminal
labelled
P1
.
• The mixer valve actuator is connected to the
terminal labelled
ACTUATOR
.
• The optional switchover valve actuator is connected
to the terminal labelled
P2/COLD
.
• The optional heating/cooling switch is connected to
the terminal labelled
ROOMSTAT
(terminal
In1
or
In2
).
• The optional return temperature sensor is connected
to the terminal labelled
WATER RETURN
.
See section 5.4 Connect components to controller for
more information.
See also the wiring diagram in the end of the manual.
Example specific system parameter settings
• Set parameter 0 – Type of installation to
rEv
if it is a
heating/cooling system.
• Set parameter 4 – Type of system to
Act
if the
optional switchover valve is installed.
• Set parameter 4 – Type of system to
SEP
if the
optional switchover valve is not installed.
• Set parameter 5 – Thermostat selection to
no
(to
utilise the boost function) The boost function can
only be used in systems with a return sensor, and
without a wireless thermostat).
• Set parameter 7 – Boost function to an appropriate
value, for the system (requires parameter 5 being
set to no and is used in systems with a return
sensor, and without a wireless thermostat).
• Set parameter 11/12 – Wired input 1/2 selection
to
HC
if a heating/cooling switch (option 1) is
connected to the controller.
See section 8.6 System parameter settings for more
information.
See section 6.9 Register thermostats to the controller for
more information about registering a thermostat to the
Move PLUS controller.