Chapter 7
Making a ProPEX connection
Uponor ProPEX ASTM F1960 (CAN/CSA B137.5)
cold-expansion fittings make solid, permanent,
manufactured connections without the need
for torches, glues, solder, flux, or gauges. The
unique shape memory of Uponor PEX
piping forms a tight seal around the
fitting, creating a strong, reliable
connection.
This chapter shows how
to make proper ProPEX connections using
one of the following tools.
• Milwaukee M12, M12 FUEL, or M18 ProPEX expansion tools
• Milwaukee M18 FORCE LOGIC ProPEX Expansion Tool
• ProPEX 201 Corded Expander Tool
• ProPEX Hand Expander Tool
Distance between fittings
Uponor requires a minimum
distance between ProPEX fittings
to avoid damaging the fittings
during installation and to protect
against elevated stress on the
pipe and fittings. Refer to Table 7-1
for the minimum distance between
fittings, which is expressed as cut
length of pipe.
General ProPEX connection tips
• If the fitting does not slide into the piping all the way to the
stop, immediately remove it from the piping and expand the
piping one final time.
Cut length of pipe
Figure 7-1: Distance between fittings
Nominal
fitting size
Cut length
of pipe
½"
2"
¾"
3"
1"
3½"
1¼"
4½"
1½"
4½"
2"
6"
2½"
7½"
3"
9"
Table 7-1: Minimum distance
between ProPEX fittings
uponor-usa.com
|
uponor.ca
l 31
Summary of Contents for AquaSAFE
Page 1: ...Uponor AquaSAFE System Installation Guide...
Page 36: ...30 l Uponor AquaSAFE System Installation Guide...
Page 54: ...48 l Uponor AquaSAFE System Installation Guide...
Page 56: ...50 l Uponor AquaSAFE System Installation Guide...
Page 62: ...56 l Uponor AquaSAFE System Installation Guide...
Page 68: ...62 l Uponor AquaSAFE System Installation Guide...
Page 71: ...uponor usa com uponor ca l 65...