Steel Body, Automatic Wood Pellet Feed Hot Water Boiler Operation and Maintenance
Manual
Installation of the tile with tile and tile makes it easier to clean.
DANGER
It is dangerous to keep combustible, flammable and easily flammable substances in the boiler
room.
Mounting Place Dimensions
The boiler room must be sized to provide the minimum dimensions around the boiler as shown in the
following illustration. When the boiler is placed, it is necessary to allow sufficient distance to be added
to the fuel tank (bunker), to be able to easily remove the burner under the bunker and to work
comfortably.
A: At least 80 cm to allow convenient use of the boiler
cleaning arm and service intervention;
B: The burner assembly is at least 100 cm;
C: At least 80 cm in order to make flue connection and
to facilitate service intervention;
D: It should be selected according to the boiler type
according to its dimensions in order to open the front
cover and use it easily.
If the above measurements are complied with, a
minimum volume requirement of 8 m
3
is provided.
A (cm)
B (cm)
C (cm)
D (cm)
Ecopel 24
80
100
80
100
Ecopel 36
80
100
80
100
Ecopel 48
80
100
80
100
DANGER
There should not be any faulty and suspicious electrical line in the boiler room.
The 230 V electrical connection from the control panel must be connected to the mains via an
automatic fuse (W automat).