EX-MANUAL-032321
21
COMMAND #130: WRITE HIGH ALARM SETPOINT
Writes the setpoint for the High Alarm
REQUEST DATA BYTES
Byte
Format
Description
0-3
Float
High Alarm Setpoint
RESPONSE DATA BYTES
Byte
Format
Description
0
Enum
PV Unit value
1-4
Float
High Alarm Setpoint
COMMAND-SPECIFIC RESPONSE CODES
Code
Class
Description
0
Success
No Command-Specific Errors
1-15
Undefined
16
Error
Access Restricted
17-31
Undefined
32
Error
Busy
33-127
Undefined