Table 6.3.1:
References to evaluate measurement results
(in compliance with DIN VDE 0413 Part 7)
State of the
earth resistance
earth resistance
ground
bar ground connection
flat ground connection
3m
deep
5m
deep
5m
long
10m
long
marshy soil/swamp
10
Ω
5
Ω
12
Ω
6
Ω
arable land/clay
33
Ω
17
Ω
40
Ω
20
Ω
humid sandy soil
66
Ω
33
Ω
80
Ω
40
Ω
dry sandy soil
330
Ω
165
Ω
400
Ω
200
Ω
stony soil
1000
Ω
500
Ω
1200
Ω
60
Ω
concrete1:5 160
Ω
80
Ω
required max. permissable resistance
maximum displayed test value
0,3
Ω
0,18
Ω
0,4
Ω
0,28
Ω
0,5
Ω
0.37
Ω
0,6
Ω
0,46
Ω
0,7
Ω
0,56
Ω
0,8
Ω
0,65
Ω
0,9
Ω
0,75
Ω
1,0
Ω
0,84
Ω
2,0
Ω
1,85
Ω
3,0
Ω
2,79
Ω
4,0
Ω
3,73
Ω
5,0
Ω
4,67
Ω
For a required earth resistance as shown in Table 6.3.1, the measured value must not
exeed the values in the table below taking into account instrument error.