Commissioning
Q3 15-150A
10/2018 - V01
28
Commis
si
oni
ng
Q3
x
/x
-x wi
th
RE
G
4
6
Commissioning
6.1
Commissioning Q3 x/x-x with REG4
Check the following connections before commissioning
Observe the type plate!
Basic connection - power connections Q3
Power supply
power
bolts X10:14, X10:15, X10:16
Power supply
auxiliary voltage
terminals X5:17, X5:18
Power supply
field
terminals X5:20, X5:21
Motor connection
A1/A2
bolts X10:10, X10:13
Field connection
F1/F2
terminals X5:22, X5:23
Field current signal
terminals X5:24, X5:25
Protecting earth
PE
earthing screws PE on the
housing
Control connections
Enable
contact between X1:3 and X1:4
Command value
signal X1:6, GND X1:8a
Actual value
signal X1:9, GND X1:8b
Shields
X1:8
Control electronics REG4
Switch
S4
PI amplification
position 4
Switch
S5
I-term
position 4
Switch
S8
D amplification
position 8
Switch
S9
actual value
position 8
Potentiometer
I
1
peak current
10%
Potentiometer
I
2
peak current
10%
Potentiometer
ID
continuous current
100%
Potentiometer
X
P
amplification
50%
Potentiometer
INT
integrator
left full scale
Potentiometer
n
max
speed
left full scale
Potentiometer
offset
offset
50%