Electrical installation
15
10/2018 - V01
Q3 15-150A
CE
-Advi
ce
4.3
CE-Advice
The devices adhere to the EU guidelines 89/336/EWG and the technical standards EN 61000-2 and
61000-4 provided that the following conditions are observed:
- The device, transformer and filter capacitors are mounted on a 800x800x2mm mounting plate
- The mounting plate must be connected to ground using a 10mm² wire.
- The motor housing must be connected to ground using a 10mm² wire.
- The device ground X1:8 must be connected to the mounting plate using a 2.5mm² wire.
- Device PE screw must be connected to the mounting plate using a 4mm² wire, I = 50mm.
Three-phase connection:
Power choke type:
see technical details
Filter capacitors:
0.5mF/600V~ 3 x 1µF (x) + 1 x 1µF (y)
Conductor length between the device and the power choke <250mm
Motor connection:
Motor conductors
l = 1.5m, shielded
Tacho and all control lines
l = 1.5m, shielded
Shielding connected to PE