Electrical installation
Q3 15-150A
10/2018 - V01
18
Opt
ion
–
ex
ter
na
l sy
nch
roni
zat
ion
4.6
Option – external synchronization
For special applications it might be necessary to tap the synchronization before the power
commutating choke, e.g.
- when operating via field triggering circuit
- in case of an instable power supply
Q3-M656-ext-synch-15-40
Q3-ext-synch-anschluss-v647
The wiring has to be short-circuit proof or protected means of a line protection.
Connection across the terminals X18:35, 36, 37
Observe the phase position!
- L3 across X10:14 (via power choke) and directly across terminal X18:36
- L2 across X10:15 (via power choke) and directly across terminal X18:37
- L1 across X10:16 (via power choke) and directly across terminal X18:35
Attention:
If incorrectly connected at X18 – the device can be destroyed