3.7.3. Door
When the user selects
◆
[ENT~]
[5. Terminal]
[3. Door] in the initial screen
◆
,
the following screen will appear.
▶
Initial setting: Identical with the screen at the left
▶
Lock Type
Set to ‘1’ when strike type or automatic door is connected with the terminal while ‘2’
when motor lock is connected to the terminal. In case that no connection is made, it is
also set to ‘1’. Set to ‘3’ when connecting the warning lamp to the lock port to indicate
the success or failure of authentication.
▶
Door Monitor
Set this function to know the door status
- ‘3.Disable’ – when not checking the door status
- ‘1.Normal Open’: In the case of dead bolt type or automatic door
(When lock monitoring is open where the door is locked)
- ‘2.Normal Close’: In the case of Strike type
(When lock monitoring is locked where the door is locked)
▶
Open Duration (0.1 sec unit)
It designates the time that the door is opened and closed again when authentication is
successful. As it is set to 0.1 second unit, a value of 30 is required to set it to 3 seconds.
Strike type refers to the time the door is opened and closed again when authentication
is complete.
▶
Warn Door Open (Second unit)
This is the function that enables the terminal to check the time of the door being
opened, and generates a warning sound once it exceeds the preset time (min. 5 sec~
max 30 sec).
When set to ‘00’, warning doesn’t sound at all. Even if set to 01~04, it starts sounding
when it exceeds at least 5 seconds.
The warning sound is also generated in case the door is not closed unexpectedly
within the preset time although the door should be closed. It allows for a proper action
to be taken for the door to be closed by informing about the fact that the door is not
closed.
To operate this function, the lock must be the one that enables to monitor
the door status and the monitoring pin of lock should be connected to the terminal
without fail. In addition, such settings are enabled only when the aforementioned Door
Monitor is set to ‘4. Normal Open’ or ‘5.Normal Close’.