18
Note:
Siemens QBE2...P pressure probes send a 0-10 Volt output signal, while Danfoss MBS3200... pressure probes send a 4-20 mA
output signal.
Connecting 100 ohm / 1000 ohm temperature probes
directly to LMV terminals
Connecting 0...10V / 4...20 mA / 0...20 mA pressure probes
directly to LMV terminals
Temperature probes on burner control panel
Pressure probes on burner control panel
Terminals
Description
Terminals
Description
LMV
Burner
LMV
Burner
X60.5
SCH
Functional earth for shield connec-
tion
X61.5
SCH
Probe cable screen
X60.3
13C Temperature
probe
1000
Ω
X61.1
13A
Power aupply for temp./pressure
probe
X60.1
13D
Temperature probe 100
Ω
X61.2
13
Voltahe input (0..10Volt)
X60.2
13B
Compensation line
X61.3
13G
Current input (0/4..20mA)
X60.4
12A
Reference ground
X61.4
12
Reference ground
Connecting 100 ohm / 1000 ohm temperature sensors to
burner teminals
Connecting 0...10V / 4...20 mA / 0...20 mA pressure sensors
to burner teminals
X60.5
Functional earth for
shield connection
X60.2
X60.4
Line compensation
Pt100
Reference ground
X60.3
X60.1
Temperature sensor
Pt/LG-Ni 1000 (input 4)
Temperature sensor
Pt 100 (input 1)
Pt 100
Pt/LG-Ni 1000
TEMP.
-
Temperature/pressure controller
LMV5...
-
X61.5
Functional earth for
shield connection
X61.3
X61.4
Current input
4...20 mA (input 2)
Reference ground
X61.1
X61.2
Power supply for temp./
pressure transmitter
Voltage input
DC 0...10 V (input 2)
TEMP./PRES. INPUT
4...20mA
0...10 V
U
I
+
+
-
/ p
-
/ p
Summary of Contents for P60 VS
Page 45: ...Service manual Siemens LMV 5x M12920CB Rev 1 08 2009...
Page 46: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 97: ...User manual Siemens LMV 5x M12914CA Rev 0 03 2008...
Page 98: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 114: ...Annex1 Example for motor cable...
Page 115: ......
Page 116: ...Annex 2 Example for sensor cable...
Page 117: ......
Page 118: ......
Page 122: ......